| Plan Review Notes For Permit 05080400 |
| Permit Number |
05080400 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-16 00:00:00 | DENIED | | | | | | 1) PLANS ARE NOT CLEAR ON WALL TYPES. | | | DETAIL 2 ON A8.0 SPECIFIES WALL TYPE 'B' | | | AS A NON RATED FULL HEIGHT PARTITION. | | | HOWEVER, BELOW THE DETAIL A NOTE | | | SPECIFIES 1-HOUR RATED TENANT SEPARATION | | | WALL UL DESIGN U 465. | | | | | | 2) SPECIFY THE THICKNESS AND TYPE OF | | | GYPSUM WALL SHEATHING ON THE DETAILS. | | | | | | 3) SPECIFY THE RATING OF THE DOORS AND | | | CLOSER TYPE FOR DOORS IN THE FIRE RATED | | | PARTITIONS. SEE FBC 705.1.3.1 AND | | | 705.1.3.5. | | | | | | 4) SPECIFY THE RATING OF DOORS 200A IN | | | THE RELOCATED PARTITION (WALL TYPE 'B') | | | AT THE TV CONTROL ROOM. | | | | | | 5) SPECIFY THAT SIGNS OR STENCILING WILL | | | BE PROVIDED AS REQUIRED BY FBC | | | 704.2.1.4. | | | | | | 6) ADDRESS COMMENTS FROM OTHER | | | REVIEWERS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|