Plan Review Notes
Plan Review Notes For Permit 05080400
Permit Number 05080400
Review Stop B
Sequence Number 1
Notes
Date Text
2005-08-16 00:00:00DENIED
  
 1) PLANS ARE NOT CLEAR ON WALL TYPES.
 DETAIL 2 ON A8.0 SPECIFIES WALL TYPE 'B'
 AS A NON RATED FULL HEIGHT PARTITION.
 HOWEVER, BELOW THE DETAIL A NOTE
 SPECIFIES 1-HOUR RATED TENANT SEPARATION
 WALL UL DESIGN U 465.
  
 2) SPECIFY THE THICKNESS AND TYPE OF
 GYPSUM WALL SHEATHING ON THE DETAILS.
  
 3) SPECIFY THE RATING OF THE DOORS AND
 CLOSER TYPE FOR DOORS IN THE FIRE RATED
 PARTITIONS. SEE FBC 705.1.3.1 AND
 705.1.3.5.
  
 4) SPECIFY THE RATING OF DOORS 200A IN
 THE RELOCATED PARTITION (WALL TYPE 'B')
 AT THE TV CONTROL ROOM.
  
 5) SPECIFY THAT SIGNS OR STENCILING WILL
 BE PROVIDED AS REQUIRED BY FBC
 704.2.1.4.
  
 6) ADDRESS COMMENTS FROM OTHER
 REVIEWERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  