| Plan Review Notes For Permit 05080390 |
| Permit Number |
05080390 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-03 00:00:00 | ************* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE PLANS INDICATE | | | RE-FEEDING THE ENTIRE SERVICE. PLEASE | | | PROVIDE LOADS CALCULATIONS PER 220.31B | | | | | | | | | PLEASE SEE SPECS INDICATE THIS UNIT | | | RATED 167A'S WITH LP AS THE PRIME MOVER. | | | PLEASE SEE NATURAL GAS IS BEING USED AND | | | GENERATED IS NOT RATED FOR THE SAME | | | AMERAGE. | | | PLEASE PROVIDE LOAD CALCS AS ABOVE FOR | | | INTENDED LOADS. | | | PLEASE KNOW, IF AUTOMATIC LOAD SHEEDING | | | OF "HEAT" ON A/C SYSTEMS IS | | | NOTED/DETAILED AND PROVIDE. HEAT LOAD | | | AND AND ANY OTHER "SHEDDED" ITEMS MAY BE | | | REMOVED FROM LOAD CACULATIONS. | | | 215.5,700.5, 702.5 | | | | | | 2)NOTE: PLEASE SEE GEN SPEC SHEETS | | | SUBMITTED SHOWS ARROW TO 40KW UNIT, | | | HOWEVER NG CIRCILED FOR 30KW ALSO? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|