| Plan Review Notes For Permit 05080390 |
| Permit Number |
05080390 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-24 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. GENERATOR MANF. RECOMBINATIONS FOR | | | SERVICE CLEARANC /VENILATION IN | | | FEET/INCHES IN ALL DIRECTION MUST ACCOM. | | | GENERATOR PERMIT APP.NEC 70 110.3 B. | | | | | | 2.GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENING, AND | | | EXHAUST MUST BE DIRECTED AWAY FROM | | | BUILDING.AND BE TEN FEET FROM PROPETY | | | LINE.2001 FBC/M 804.3.3 TERMINATION. | | | 2001 FBC/M SECTION 915 8.2.3.2 | | | EXHAUST SYSTEM TERMINATION. | | | | | | 3. LP/NAT GAS REQUIRES PERMIT, FROM | | | LICENSED GAS CONTRACTOR. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|