Plan Review Notes
Plan Review Notes For Permit 05080355
Permit Number 05080355
Review Stop E
Sequence Number 4
Notes
Date Text
2006-03-30 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE MININUM FEEDER SIZES
 AND MAX OCP FOR FEEDERS TO SUB PANEL.
 PLEASE SEE310.15B6, WHICH PERMITS
 FEEDERS TO BE DERATED FOR A 120/240
 RESIDENTIAL SERVICE, HOWEVER #3'S ARE
 SHOWN WHICH ARE ONLY RATED FOR 110A'S.
 THE NEC DOES PERMIT TO GO TO THE NEXT
 HIGHER SIZE OCP WHEN A DEVICE DOES NOT
 CORRELATE WITH THE AMERAGE. PLEASE SEE
 240.6, 110A'S IS A COMMON OCP SIZE.
 PLEASE EITHER INCREASE FEEDER OR ADJUST
 MAX OCP.
 215.5
  
 2) NOTE: PLEASE SEE PLANS INDICATE A
 PANEL IN GARAGE BUT DOES NOT INDICATE
 WHICH ONE. IT IS UNCLEAR WHICH PANEL
 THIS IS. PLEASE SEE THREE PANELS ARE
 SHOWN ON RISER AND ONLY TWO ON PLANS?
 (POOL PANEL IS LABELED).
 215.5
  
 3) NOTE: PLEASE SEE 240.24,310.16.
 PLEASE SEE WHIRL-POOL TUB SHOWS 40A OCP
 ON #10 AWG.
  
 4) NOTE: PLEASE VERIFY HP RATINGS FOR
 GDO'S. PLANS SHOW TWO , HOWEVER ONLY ONE
 CIRCUIT IS SHOWN IN PANEL.
 PLEASE SEE 430.24, 430.148
 IF HP RATINGS ARE 1/3 HP AND ABOVE, THEN
 A DEDICATED CIRCUIT WOULD BE REQUIRED
 FOR EACH.
  
 ** PLEASE SUBMIT THEABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]