| Plan Review Notes For Permit 05080355 |
| Permit Number |
05080355 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-10-13 00:00:00 | ******* PROVISO/REVISION REQUIRED ***** | | | | | | | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BEWTEEN MAIN | | | DISCONNECT AND SUB PANEL "A". | | | 250.24,250.110,250.122 | | | | | | 2)NOTE: PLEASE SEE TABLE 9 NEC FOR MIN | | | CONDUIT SIZE PER CONDUCTOR SIZES AND | | | NUMBER OF CONDUCTORS WITH RESPECT TO | | | TYPE OF CONDUIT. | | | PLEASE SEE CONDUIT FOR POOL SUB PANEL | | | SHALL BE INCREASED TO 1 1/4 MIN. | | | | | | 3)NOTE: PLEASE SEE CONTINUOUS LOADS FOR | | | POOL HEATER AND POOL PUMP NOT CLEAR. | | | 215.3,230.42 ETC. | | | | | | PLEASE REVISE THE ABOVE INFORMATION FOR | | | REVIEW ALONG WITH ANY OTHER | | | CHANGES/REVSIONS ON PLANS. PLEASE BE | | | SURE PLANS ARE SUBMITTED FOR REVIEW AND | | | STAMPING TO BE ON SITE BEFORE "ROUGH" | | | ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|