Plan Review Notes
Plan Review Notes For Permit 05080355
Permit Number 05080355
Review Stop E
Sequence Number 3
Notes
Date Text
2005-10-13 00:00:00******* PROVISO/REVISION REQUIRED *****
  
  
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BEWTEEN MAIN
 DISCONNECT AND SUB PANEL "A".
 250.24,250.110,250.122
  
 2)NOTE: PLEASE SEE TABLE 9 NEC FOR MIN
 CONDUIT SIZE PER CONDUCTOR SIZES AND
 NUMBER OF CONDUCTORS WITH RESPECT TO
 TYPE OF CONDUIT.
 PLEASE SEE CONDUIT FOR POOL SUB PANEL
 SHALL BE INCREASED TO 1 1/4 MIN.
  
 3)NOTE: PLEASE SEE CONTINUOUS LOADS FOR
 POOL HEATER AND POOL PUMP NOT CLEAR.
 215.3,230.42 ETC.
  
 PLEASE REVISE THE ABOVE INFORMATION FOR
 REVIEW ALONG WITH ANY OTHER
 CHANGES/REVSIONS ON PLANS. PLEASE BE
 SURE PLANS ARE SUBMITTED FOR REVIEW AND
 STAMPING TO BE ON SITE BEFORE "ROUGH"
 ELECTRICAL INSPECTION.
  