| 2005-09-20 00:00:00 | ********* UNSAT ********* |
| | |
| | PLEASE SEE NEW NOTES DUE TO CHANGE IN |
| | PLANS AND RISER DIAGRAM. |
| | |
| | |
| | 1)NOTE: PLEASE SEE NEW RISER NOW SHOWS A |
| | NEW POOL PANEL, PLEASE CORRELATE FEEDERS |
| | SHOWN ON RISER (#3) AND PANEL SCHEDULE |
| | "A" (#2). |
| | PLEASE SEE FOLLOWING COMMENT |
| | |
| | 2)NOTE: PLEASE SHOW LOCATION OF NEW POOL |
| | PANEL ON PLANS. THIS COULD NOT BE |
| | LOCATED.? |
| | |
| | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | @125%, (HEAT PUMP AND POOL PUMP) THESE |
| | LOADS ARE 3 OR MORE HRS. |
| | PLEASE ADJUST LOAD CALCUALTIONS ON PANEL |
| | AND SERVICE. |
| | 215.3,230.42 ETC. |
| | |
| | 4)NOTE: PLEASE SEE NOTE WAS ADDED FOR |
| | ARC-FAULT PROTECTION PER 210.12, HOWEVER |
| | PLEASE SEE THE NEC REFERENCED IS 2004? |
| | PLEASE SEE THIS SHOULD READ 2002. |
| | |
| | 5)NOTE: PLEASE SEE POOL PANEL SCHEDULE, |
| | WHICH INDICATES AHU AS HEAT? PLEASE SEE |
| | MECH PLANS INDICATE THIS UNIT AS COOL |
| | ONLY. PLEASE CORRELATE. |
| | PLEASE ALSO SEE KW HEAT LOADS ON |
| | MECHANICAL PLANS AND ELECTRICAL PLANS. |
| | PLEASE CORRELATE AND ADJUST LOAD |
| | CALCULATIONS. |
| | 220,215.5 |
| | |
| | 6)NOTE: PLEASE SEE LOAD CALCULATIONS AS |
| | SHOWN WITH OUT INCREASE FOR CONTINUOUS |
| | LOADS OR LOAD FOR AHU'SAND LOADS |
| | ALREADY AT 194A'S WITH ALLPERMITTED |
| | DE-RATINGS. |
| | PLEASE SEE SERVICE SIZE WILL BE REQUIRED |
| | TO BE INCREASED TO A MIN 225A'S |
| | DEPENDING ON OUTCOME OF ADJUSTED LOAD |
| | CALCUALTIONS. |
| | PLEASE SEE PANELS, SERVICES ETC ALL |
| | SHALL BE SIZED FOR "FUTURE EXPANSION" OF |
| | LOADS , SPACES. |
| | 90.8 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |