| Plan Review Notes For Permit 05080355 |
| Permit Number |
05080355 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-23 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. BEDROOMS #2 #3 #5 REQUIRE R/A OUT | | | OF ROOMS. FBC/M 601.4 | | | | | | 2. A/C SYSTEM #3 NOT REFLECTED ON A/C | | | PLANE BUT SHOWN ON A-1 SHEET. | | | | | | 3. A/C ENERGY SEER RATING NOT | | | REFLECTED WITH A/C EQUIPMENT. | | | | | | 4. A/C #3 NOT REFLECTED ON ELECTRICAL | | | PANEL OR A/C EQUIPMENT INFORMATION. | | | | | | | | | 5. BATHROOM EXHAUST FANS NOT SIZEDON | | | A/C OR ELECTRICAL PLANS PLEASE CORRECT. | | | | | | 6. CLOTH DRYER VENT NOT SIZED OR | | | REFLECTED ON A/C PLANS. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|