Plan Review Notes
Plan Review Notes For Permit 05080355
Permit Number 05080355
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-17 00:00:00 
 ******** UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO
 SUB-PANEL.
 250.110,250.24 SIZED PER 250.122
  
 3)NOTE: PLEASE SEEMISSING RECEPTSON
 PLANS PER 210.52. PLEASE SEE SOME OF
 THESE AREAS ARE REDLIEND ON ONE SET OF
 PLANS.
  
 4)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 2002 NEC 210.12
  
 5)NOTE: PLEASE PLACE THE ROOM AND AREA
 DESIGNATIONS ON PLANS.
  
 6)NOTE: PLEASE SEE BLDG COMMENTS IN REF
 TO SURVEY REQUIRING THE ORIGINAL
 SIGNATURE AND RAISED SEAL FOR SURVEYOR.
 FS 472.025, FAC 61G17-17.002
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  