| 2005-08-17 00:00:00 | |
| | ******** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO |
| | SUB-PANEL. |
| | 250.110,250.24 SIZED PER 250.122 |
| | |
| | 3)NOTE: PLEASE SEEMISSING RECEPTSON |
| | PLANS PER 210.52. PLEASE SEE SOME OF |
| | THESE AREAS ARE REDLIEND ON ONE SET OF |
| | PLANS. |
| | |
| | 4)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE SEE 2002 NEC 210.12 |
| | |
| | 5)NOTE: PLEASE PLACE THE ROOM AND AREA |
| | DESIGNATIONS ON PLANS. |
| | |
| | 6)NOTE: PLEASE SEE BLDG COMMENTS IN REF |
| | TO SURVEY REQUIRING THE ORIGINAL |
| | SIGNATURE AND RAISED SEAL FOR SURVEYOR. |
| | FS 472.025, FAC 61G17-17.002 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |