| 2005-08-26 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) DETAIL 16 ON S4 SPECIFIES A USP |
| | KST237 STRAP WITH ONE NED FASTENED TO |
| | MASONRY WITH TAP CONS. THE 2005 CATALOG |
| | LISTS THIS AS A WOOD TO WOOD CONNECTOR. |
| | SUBMIT A LETTER OR BULLETIN FROM USP |
| | THAT WILL ALLOW THIS APPLICATION. |
| | |
| | 3) CONNECTION DETAIL 11 ON S4 LISTS |
| | DIFFERENT NUMBERS OF FASTENERS FOR THE |
| | HUC HANGERS THAN ARE SPECIFIED IN THE |
| | 2005 USP CATALOG. SEE PAGE 128. |
| | |
| | 4) THE CONCRETE NOTES ON G1 LISTS THE |
| | WRONG EDITIONS OF ACI 318 AND 530. FBC |
| | CHAPTER 35 REFERENCES THE 2002 EDITIONS. |
| | |
| | 5) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT THE |
| | FL COVER SHEET FOR THE FIXED WINDOWS. |
| | |
| | 6) THE WINDOWS AT THE TUB IN THE MASTER |
| | BATH ARE REQUIRED TO HAVE SAFETY |
| | GLAZING. SEE FBC 2405.2. |
| | |
| | 7) SUBMIT PRODUCT APPROVALS INCLUDING |
| | THE FLORIDA COVER SHEETS FOR THE |
| | STRUCTURAL MULLIONS, THE TRUSS |
| | CONNECTORS AND ENTRY PANEL DOORS. |
| | |
| | 8) SPECIFY ON THE PLANS HOW THE ROOF |
| | TILES WILL BE FASTENED TO RESIST THE |
| | REQUIRED UPLIFT MOMENT REQUIRED BY THE |
| | TABLES LISTED ON PAGES 8 AND 9 IN THE |
| | PRODUCT APPROVAL BASED ON EXPOSURE |
| | CATEGORY. |
| | |
| | 9) THE EXPOSURE CATEGORY LISTED ON G1 IS |
| | INCORRECT. SHORELINES IN HURRICANE |
| | REGIONS ARE EXCLUDED. SEE ASCE7-98. |
| | |
| | 10) THE OVERHEAD GARAGE DOOR |
| | INSTALLATION DRAWINGS ARE ILLEGIBLE. |
| | SUBMIT CLEAR LEGIBLE DRAWINGS. |
| | |
| | 11) THE FLORIDA COVERSHEET THAT WAS |
| | SUBMITTED FOR THE SH-701 SINGLE HUNG |
| | WINDOWS IS NOT THE CORRECT ONE. IT IS |
| | FOR ANOTHER MODEL OF WINDOW. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |