2005-08-26 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) DETAIL 16 ON S4 SPECIFIES A USP
 KST237 STRAP WITH ONE NED FASTENED TO
 MASONRY WITH TAP CONS. THE 2005 CATALOG
 LISTS THIS AS A WOOD TO WOOD CONNECTOR.
 SUBMIT A LETTER OR BULLETIN FROM USP
 THAT WILL ALLOW THIS APPLICATION.
  
 3) CONNECTION DETAIL 11 ON S4 LISTS
 DIFFERENT NUMBERS OF FASTENERS FOR THE
 HUC HANGERS THAN ARE SPECIFIED IN THE
 2005 USP CATALOG. SEE PAGE 128.
  
 4) THE CONCRETE NOTES ON G1 LISTS THE
 WRONG EDITIONS OF ACI 318 AND 530. FBC
 CHAPTER 35 REFERENCES THE 2002 EDITIONS.
  
 5) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT THE
 FL COVER SHEET FOR THE FIXED WINDOWS.
  
 6) THE WINDOWS AT THE TUB IN THE MASTER
 BATH ARE REQUIRED TO HAVE SAFETY
 GLAZING. SEE FBC 2405.2.
  
 7) SUBMIT PRODUCT APPROVALS INCLUDING
 THE FLORIDA COVER SHEETS FOR THE
 STRUCTURAL MULLIONS, THE TRUSS
 CONNECTORS AND ENTRY PANEL DOORS.
  
 8) SPECIFY ON THE PLANS HOW THE ROOF
 TILES WILL BE FASTENED TO RESIST THE
 REQUIRED UPLIFT MOMENT REQUIRED BY THE
 TABLES LISTED ON PAGES 8 AND 9 IN THE
 PRODUCT APPROVAL BASED ON EXPOSURE
 CATEGORY.
  
 9) THE EXPOSURE CATEGORY LISTED ON G1 IS
 INCORRECT. SHORELINES IN HURRICANE
 REGIONS ARE EXCLUDED. SEE ASCE7-98.
  
 10) THE OVERHEAD GARAGE DOOR
 INSTALLATION DRAWINGS ARE ILLEGIBLE.
 SUBMIT CLEAR LEGIBLE DRAWINGS.
  
 11) THE FLORIDA COVERSHEET THAT WAS
 SUBMITTED FOR THE SH-701 SINGLE HUNG
 WINDOWS IS NOT THE CORRECT ONE. IT IS
 FOR ANOTHER MODEL OF WINDOW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  