| Plan Review Notes For Permit 05080350 |
| Permit Number |
05080350 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | PROVISO: | | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 | | | FBC(M)307.2.3. | | | | | | 2.CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12" FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | 3.PER 2001 FBC(M)603.15, BALANCING | | | DAMPERS OR OTHER MEANS OF SUPPLY | | | ADJUSTMENT SHALL BE PROVIDED IN THE | | | BRANCH DUCTS OR INDIVIDUAL DUCT | | | REGISTER, GRILLE OR DIFFUSER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|