Plan Review Notes
Plan Review Notes For Permit 05080350
Permit Number 05080350
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-09 00:00:00PROVISO:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 2.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 3.PER 2001 FBC(M)603.15, BALANCING
 DAMPERS OR OTHER MEANS OF SUPPLY
 ADJUSTMENT SHALL BE PROVIDED IN THE
 BRANCH DUCTS OR INDIVIDUAL DUCT
 REGISTER, GRILLE OR DIFFUSER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.