| Plan Review Notes For Permit 05080294 |
| Permit Number |
05080294 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-18 00:00:00 | DENIED | | | | | | 1) CORRECT THE PLYWOOD SHEATHING NAILING | | | SCHEDULE FOR ROOF TO SPECIFY 5/8" | | | PLYWOOD. | | | | | | 2) THE BUILDING CATEGORY IS II. THE | | | BUILDING CATEGORY IS SPECIFIED AS OPENED | | | ON THE PLAN. DID YOU INTEND TO SPECIFY | | | THE EXPOSURE CATEGORY AS OPEN. IF | | | EXPOSURE CATEGORY IS OPEN THE INTERNAL | | | PRESSURE COEFFICIENT IS 0.00. SEE ASCE | | | 7- 98. PLEASE CORRECT THIS INFORMATION. | | | | | | 3) PROVIDE STRUCTURAL DETAILS FOR THE | | | EXTERIOR WINDOW OPENING AND THE SLIDING | | | GLASS DOOR OPENING. | | | | | | 4) PROVIDE A DETAIL OF THE EXTERIOR WALL | | | SPECIFYING THE CONSTRUCTION USED TO | | | ENCLOSE THE WINDOW OPENINGS. | | | | | | 5) SUBMIT STATE PRODUCT APPROVALS FOR | | | THE SINGLE HUNG WINDOWS. | | | | | | 6) SPECIFY WHICH ONE OF THE APPROVED | | | ASSEMBLIES FROM THE ROOFING PRODUCT | | | APPROVAL WILL BE INSTALLED. CIRCLE THE | | | APPROPRIATE ASSEMBLY IN THE NOA. | | | | | | 7) SPECIFY THE CONNECTION TYPE, THE | | | FASTENER TYPE AND FASTENER SPACING FOR | | | THE STORM PANELS. | | | | | | 8)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | |
|