2005-08-18 00:00:00DENIED
  
 1) CORRECT THE PLYWOOD SHEATHING NAILING
 SCHEDULE FOR ROOF TO SPECIFY 5/8"
 PLYWOOD.
  
 2) THE BUILDING CATEGORY IS II. THE
 BUILDING CATEGORY IS SPECIFIED AS OPENED
 ON THE PLAN. DID YOU INTEND TO SPECIFY
 THE EXPOSURE CATEGORY AS OPEN. IF
 EXPOSURE CATEGORY IS OPEN THE INTERNAL
 PRESSURE COEFFICIENT IS 0.00. SEE ASCE
 7- 98. PLEASE CORRECT THIS INFORMATION.
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE
 EXTERIOR WINDOW OPENING AND THE SLIDING
 GLASS DOOR OPENING.
  
 4) PROVIDE A DETAIL OF THE EXTERIOR WALL
 SPECIFYING THE CONSTRUCTION USED TO
 ENCLOSE THE WINDOW OPENINGS.
  
 5) SUBMIT STATE PRODUCT APPROVALS FOR
 THE SINGLE HUNG WINDOWS.
  
 6) SPECIFY WHICH ONE OF THE APPROVED
 ASSEMBLIES FROM THE ROOFING PRODUCT
 APPROVAL WILL BE INSTALLED. CIRCLE THE
 APPROPRIATE ASSEMBLY IN THE NOA.
  
 7) SPECIFY THE CONNECTION TYPE, THE
 FASTENER TYPE AND FASTENER SPACING FOR
 THE STORM PANELS.
  
 8)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  