| 2005-09-22 00:00:00 | BLDG #11DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| | FLOOD ZONE. AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. |
| | |
| | 3) ADDITIONAL PERMIT FEES ARE DUE. THE |
| | CALCULATED VALUE OF THE STRUCTURE IS |
| | $674,294.00. A WESTWARD EXPANSION FEE OF |
| | $550.00 PER UNIT IS ALSO REQUIRED. |
| | |
| | 4) THE SITE PLANS ARE REQUIRED WHICH |
| | SPECIFY THE DISTANCE TO ASSUMED PROPERTY |
| | LINES BETWEEN ADJACENT BUILDINGS LOCATED |
| | ON THE SAME LOT. THIS IS REQUIRED IN |
| | ORDER TO DETERMINE THE PERCENTAGE OF |
| | WALL AREA THAT IS ALLOWED AS OPENINGS BY |
| | FBC TABLE 600. |
| | |
| | 5) THESE UNITS DO NOT MEET THE |
| | DEFINITION OF TOWNHOUSE IN THE 2001 |
| | FLORIDA BUILDING CODE. PLEASE REMOVE THE |
| | TITLE OF TOWNHOMES FROM THE TITLE BLOCKS |
| | OF THE M.E.P. DRAWINGS. |
| | |
| | 6) SPECIFY THE SCALE OF THE DRAWINGS ON |
| | THE PLANS. |
| | |
| | 7) SPECIFY THE OCCUPANCY, CONSTRUCTION |
| | TYPE, PROTECTED OR UNPROTECTED AND |
| | SPRINKLERED OR UNSPRINKLERED. |
| | |
| | 8)CONDOMINIUM V APARTMENTS.IF THE |
| | DWELLING UNITS ARE TO BE SOLD AS |
| | CONDOMINIUMS, A 'DECLARATION OF |
| | CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| | STATE FOR APPROVAL, AND THEN RECORDED |
| | WITH THE CLERK OF THE COUNTY COURT.A |
| | RECORDED COPY SHALL BE SUBMITTED TO THE |
| | CITY FOR RECORDS, ADDRESSING PURPOSES, |
| | AND TO PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S OFFICE PRIOR TO C.O. |
| | |
| | 9) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 10) FBC 705.1.3.2.1 CLASSIFIES FIRE |
| | DOORS AS 3 HOUR, 1-2/2 HOUR, 1 HOUR, 3/4 |
| | HOUR OR 20 MINUTE. REVISE THE 'C' LABEL |
| | DOOR SPECIFIED ON SHEET A9. FBC |
| | 705.1.3.2.2 ALLOWS 20 MINUTE RATED DOORS |
| | IN WALLS REQUIRED TO HAVE A FIRE |
| | RESISTANCE RATING OF 1 HOUR OR LESS. |
| | |
| | 11) FBC 705.1.3.5 REQUIRES FIRE DOORS TO |
| | BE EQUIPED WITH AN APPROVED CLOSER. |
| | |
| | 12) PROVIDE A ROOF SHEATHING NAILING |
| | PLAN FOR THE LOWER ROOFS THAT ARE NOT |
| | SHOWN ON S4. |
| | |
| | 13) THE SPACING OF THE TAPCON FASTENERS |
| | FOR THE GARAGE DOOR HEADER IN DETAIL 1 |
| | ON S4 APPEAR TO CONFLICT. 16"OC IS |
| | SPECIFIED IN ONE PLACE AND 8" OC IS |
| | SPECIFIED UNDER NOTES. PLEASE CORRECT. |
| | |
| | 14) FBC TABLE 1604.1 REQUIRES THE BOTTOM |
| | CORD LIVE LOAD TO BE 10 PSF FOR ATTICS |
| | WITHOUT STORAGE AND 30 PSF FOR ATTICS |
| | WITH STORAGE. REVISE ROOF LOADS ON S5. |
| | |
| | 15) UNDER GENERAL NOTES ON S5, ITEM # 24 |
| | SPECIFIES THE WRONG EDITIONS OF ACI, |
| | ASCE 5 AND TMS. THE 2002 EDITIONS ARE |
| | REFERENCED IN CHAPTER 35 OF THE 2001 FBC |
| | |
| | 16) UNDER STRUCTURAL DESIGN CRITERIA ON |
| | S5, THE CORRECT EDITIONS OF THE |
| | REFERENCE STANDARDS ARE ACI 318-02 AND |
| | ACI 5301-02. |
| | |
| | 17) THE EXTERIOR WALL SECTION 5 ON S6 |
| | SPECIFIES 6" FROM THE TOP OF THE |
| | MONOLITHIC SLAB TO FINISH GRADE. THIS |
| | WILL NOT ALLOW THE BOTTOM OF THE 16" |
| | DEEP FOOTER TO BE A MINIMUM 12" BELOW |
| | FINISH GRADE AS REQUIRED BY FBC 1804.1.3 |
| | |
| | 18) THE ROOF PITCH ON THE WALL SECTION 5 |
| | ON S6 IS SPECIFIED AS 5/12 AND THE |
| | ELEVATIONS ON A4 SPECIFY 4/12. |
| | |
| | 19) THE UL SYSTEM SPECIFIED FOR THE ONE |
| | HOUR FIRE RATED TENANT SEPARATION WALLS |
| | "U 907" IS FOR NONBEARING WALLS ONLY. |
| | PLEASE SPECIFY A SYSTEM FOR BEARING |
| | WALLS. |
| | |
| | 20) THE DRAWINGS ARE MISLABELED ON SHEET |
| | A7GR. THEY SHOULD BE GARAGE RIGHT. |
| | |
| | 21) PROVIDE A DETAIL OF THE GUARDRAILS |
| | AT THE OPEN SIDE OF THE STAIRS (LOWER |
| | SECTION). SEE FBC 1015. |
| | |
| | 22) PROVIDE AN AREA TABULATION TABLE |
| | LISTING THE FIRST AND SECOND FLOOR A/C |
| | AREAS AND UNCONDITIONED AREAS FOR EACH |
| | UNIT AND THE TOTALS FOR THE STRUCTURE. |
| | |
| | 23) THE ELEVATORS ARE REQUIRED TO COMPLY |
| | WITH ASME A17.1 AND ANSI A117.1 (FAIR |
| | HOUSING). |
| | |
| | 24) SPECIFY METHOD OF TERMITE PROTECTION |
| | AS REQUIRED BY FBC 1816. |
| | |
| | 25)PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 24) SPECIFY HOW IMPACT PROTECTION WILL |
| | BE PROVIDED FOR THE GLAZED OPENINGS AS |
| | REQUIRED BY FBC 1606.1.4. ITEM #13 OF |
| | THE CITY OF WPB IMPLEMENTATION STANDARD |
| | FOR HURRICANE MISSLE IMPACT PROTECTION |
| | REQUIRES PRE-STORM PREPARATION PLANS TO |
| | BE SUBMITTED FOR REVIEW IF USING STORM |
| | SHUTTERS, IN ADDITION TO A KEY PLAN, |
| | INSTALLATION SCHEDULE AND PRODUCT |
| | APPROVALS. STORM PANELS ARE NOT ALLOWED |
| | ABOVE THE FIRST FLOOR FOR THIS TYPE OF |
| | STRUCTURE AND OCCUPANCY. |
| | |
| | 25) SUBMIT THE EVALUATION REPORT AND |
| | INSTALLATION INSTRUCTIONS FROM NATIONAL |
| | ACCREDITATION ANS MANAGEMENT INSTITUTE |
| | FOR THE THERMA-TRU DOORS WITH FL # 1170. |
| | THE INFORMATION THAT WAS SUBMITTED TO |
| | THE STATE FOR STATE PRODUCT APPROVAL IS |
| | REQUIRED TO BE SUBMITTED WITH THE STATE |
| | COVER SHEET. |
| | |
| | 26) SUBMIT PRODUCT APPROVAL FOR THE |
| | SMALL (8' X 7') OVERHEAD GARAGE DOOR |
| | WHICH IS LESS THAN THE MINIMUM SIZE |
| | ALLOWED BY THE PRODUCT APPROVAL FOR THE |
| | LARGE DOOR THAT WAS SUBMITTED. |
| | |
| | 27) SUBMIT PRODUCT APPROVALS FOR THE |
| | TRUSS CONNECTORS. |
| | |
| | 28) THE ENGINEER'S FIRM # IS REQUIRED TO |
| | BE LISTED IN THE TITLE BLOCK. SEE FAC |
| | 61G15-23.002. |
| | |
| | 29) THE ENGINEER IS REQUIRED TO SIGN HIS |
| | NAME TO THE PLANS HE SEALS PER FAC |
| | 61G15-23.002. PLEASE SUBMIT A NOTARIZED |
| | LETTER SIGNED, SEALED AND DATED BY THE |
| | ENGINEER ATTESTING HIS LEGAL SIGNATURE. |
| | |
| | 30) THE ARCHITECT IS REQUIRED TO |
| | PERSONALLY SIGN ALL DOCUMENTS SEALED BY |
| | HIM PER FAC 61G1-16.003. PLEASE SUBMIT A |
| | NOTARIZED LETTER SIGNED, SEALED AND |
| | DATED BY THE ARCHITECT ATTESTING HIS |
| | LEGAL SIGNATURE. |
| | |
| | 31) SHOW COMPLIANCE WITH THE FAIR |
| | HOUSING ACT. ALL BUILDING ENTRANCES ARE |
| | REQUIRED TO BE ACCESSIBLE AND BE ON AN |
| | ACCESSIBLE ROUTE. |
| | - THE PRIMARY ENTRANCE DOOR MUST MEET |
| | THE REQUIREMENTS FOR ACCESSIBLE DOORS |
| | (32" CLEAR OPENING, LOW OR NO THRESHOLD- |
| | 3/4"MAX, HARDWARE COMPLYING WITH ANSI |
| | 4.13.9, ETC.) |
| | - DOORS WITHIN UNITS MUST BE USEABLE |
| | DOORS. MUST PROVIDE AT LEAST A 31-5/8" |
| | CLEAR OPENING. |
| | - CLOSET DOORS THAT REQUIRE USERS TO |
| | PASS THROUGH THE DOORWAY TO REACH THE |
| | CONTENTS MUST HAVE DOORS THAT PROVIDE AT |
| | LEAST 32 INCHES NOMINAL CLEAR OPENING. |
| | - LIGHT SWITCHES, ELECTRICAL OUTLETS, |
| | THERMOSTATS AND CONTROLS SHALL BE IN |
| | ACCESSIBLE LOCATIONS. |
| | - INDICATE THE MINIMUM CLEAR FLOOR |
| | SPACES AT THE FIXTURES AND APPLIANCES IN |
| | THE KITCHENS. |
| | - THE FAIR HOUSING ACT REQUIRES THE |
| | BATHROOMS TO BE DESIGNED TO COMPLY WITH |
| | SPECIFICATION "A" OR "B" BATHROOMS. |
| | INDICATE WHICH ONE WILL BE USED AND SHOW |
| | COMPLIANCE WITH DESIGN METHOD SELECTED. |
| | |
| | 32) SUBMIT SIGNED AND SEALED TRUSS |
| | DRAWINGS AND LAYOUTS THAT HAVE BEEN |
| | REVIEWED AND APPROVED BY THE DESIGNER OF |
| | RECORD FOR THE STRUCTURE. |
| | |
| | 33) PROVIDE STRUCTURAL DETAILS FOR THE |
| | CONCRETE STAIRS. SPECIFY THE LOCATION |
| | AND SIZE OF STEEL REINFORCEMENT IN THE |
| | LANDINGS, STAIRS AND AT TOP AND BOTTOM |
| | LOAD POINTS. |
| | |
| | 34) SUBMIT SHOP DRAWINGS FOR THE |
| | EXTERIOR GUARDRAILS. SPECIFY THE |
| | ATTACHMENTS TO THE STRUCTURE. |
| | |
| | 35) PROVIDE STRUCTURAL DETAILS OF THE |
| | INTERIOR GUARDRAIL AT THE SECOND FLOOR |
| | STAIRWELL OPENING. |
| | |
| | 36) THE STRUCTURAL PLANS DO NOT SHOW THE |
| | ELEVATOR RECESSES OR THE ELEVATOR |
| | OPENINGS AT THE SECOND FLOOR. SUBMIT |
| | STRUCTURAL DETAILS FOR THESE AREAS. |
| | |
| | 37) PROVIDE STRUCTURAL DETAILS FOR THE |
| | INFILL FLOOR FRAMING AT THE ELEVATOR |
| | RECESSES AND OPENINGS WHEN THE CLOSET |
| | OPTION IS USED IN LEIU OF THE ELEVATOR. |
| | |
| | 38) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |