| 2006-01-21 00:00:00 | PROVISO:BUILDING #5/6 UNITS | | | | | | UNIT #201 & 203 INDICATE 5 TON UNIT, | | | PER 2001 FMC 606.2.2 OR 606.4, FAN | | | SHUTDOWN REQUIRED BY DUCT SMOKE DETECTOR | | | OR BY AREA SMOKE DETECTORS.PLEASE | | | SUBMIT WHICH METHOD WILL BE USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | PER CONVERSATION WITH MIKE WILLIAMS | | | (LENNAR), M-2 PAGE INDICATES EQUIPMENT | | | SCHEDULE & WILL BE SUBMITTED FOR REVIEW. |
|