| Date |
Text |
| 2005-09-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | |
| | 1. ALL FIRST FLOOR UNITS SHALL COMPLY |
| | WITH REQUIREMENTS 1 THRU 7 OF THE FAIR |
| | HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT |
| | A DETAIL SHOWING COMPLIANCE WITH ALL |
| | REQUIREMENTS. INDICATE SPECIFICATION "A" |
| | OR "B" AS REQUIRED ON PAGE 7.34. THE |
| | CLEAR FLOOR SPACE FOR ALL USABLE |
| | FIXTURES SHALL BE APPLIED OR |
| | SUPERIMPOSED OVER THE FLOOR PLAN. FOR |
| | THE W/C SEE PAGE 7.43. |
| | 2. SHTS P1 OF 2 FOR UNITS 101, 102, 103, |
| | 201,202, & 203 MAXIMUM 6 FT. FROM SHOWER |
| | TRAP TO VENT PER TABLE 906.1. ON THE |
| | FLOOR PLAN IT SCALES OUT TO APPROX. 8' |
| | TO 9'. |
| | 3. SHTS P2 OF 2 FOR UNITS 101, 102, 103, |
| | 201, 202, & 203 WATER RISER DIAGRAM. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SOME ARE SHOWN. |
| | PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | 4. SHTS P2 OF 2 ALL UNITS WATER HEATER |
| | DETAIL. P/T DISCHARGE LINE SHALL NOT |
| | HAVE ANY TRAPED SECTIONS. SECTION |
| | 504.7.1. (SEE WATER HEATER NOTES). |
| | 5. SHTS P2 OF 2 ALL UNITS SANITARY RISER |
| | DIAGRAM. THE WASH MACHINES DRAIN LINE |
| | SHALL HAVE A STANDPIPE, SECTION 1002.1., |
| | AND THE CLEANOUT SHALL BE LOCATED 4' |
| | ABOVE THE FLOOR, SECTION 708.10 FOR |
| | ACCESS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |