| Plan Review Notes For Permit 05080275 |
| Permit Number |
05080275 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-14 00:00:00 | PLAN DENIED | | | 101,102,103 | | | 1) GARAGE EXHAUST MUST BE 10FT.FROM | | | WINDOWS AND FRESH AIR INTAKE.SECTION | | | 401.5.1 AND 501.3 FBC(M) 2001. | | | 2) PLEASE REFER TO SECTION 504.6 CLOTHES | | | DRYER DUCT.DUCT LENGTH LONGER THAN 25FT. | | | 3) PLEASE REFER TO SECTION 601.4 | | | BALANCED RETURN AIR.TRANSFER DUCT IN | | | MASTER BEDROOM IS TO SMALL.FBC(M) 2001 | | | 4)PLEASE REFER TO SECTION 301.14 FLOOD | | | RAZARD. | | | 201,203 | | | 1)PLEASE REFER TO SECTION 601.4 | | | EXCEPTION 3 TRANSFER DUCT IS NOT | | | REQUIRED IN UTILITY ROOM.FBC(M)2001 | | | 2) PLEASE REFER TO SECTION 301.14 FLOOD | | | HAZARD FBC(M)2001 | | | 3) NEED FAN SHUT DOWN SECTION 606.2.1 | | | SUPPLY AIR SYSTEM.FBC(M) 2001 | | | 202 | | | 1) PLEASE REFER TO SECTION 301.14 FLOOD | | | HAZARD FBC(M) 2001 | | | 2) PLEASE REFER TO SECTION 601.4 | | | EXCEPTION 3. BALANCED RETURN AIR | | | AIR.TRANSFER DUCT IS NO REQUIRED IN | | | UTILITY ROOM. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|