| 2005-10-06 00:00:00 | ******* UNSAT ********* |
| | |
| | PLEASE SEE ITMES LISTED BELOW WHICH WERE |
| | REQUESTED ON PREVIOUS REVIEW AND |
| | ORIGINAL REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE A/C -2 SHEET IS STILL |
| | A PHOTO-COPY OF SIGNED AND SEALED PLANS. |
| | PLEASE ALSO SEE P-SHEET IS ALSO STILL A |
| | PHOTOCOPY OF SIGNED, DATED AND SEALED, |
| | PLANS. |
| | PREVIOUS REVIEW STATED THE SAME, PLUMB |
| | SHEETS WERE PASSSED AND STAMPED IN ERROR |
| | AND NOW HAVE BEEN VOIDED. |
| | PLEASE SEE NO NEW A/C-2 SHEET WAS |
| | SUBMITTED. |
| | PLEASE SEE FS 471.025, AND FAC |
| | 61G15-23.002 |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WETHER OR NOT COMMENTS ARE |
| | MADE BY OTHER TRADES AS STATED ON |
| | PREVIOUS REVIEW. |
| | |
| | 2)NOTE: PLEASE SEE AS STATED IN THE TWO |
| | PREVIOUS REVIEWS, PLEASE REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND "INSERT" |
| | ONLY THE NEW REVISED CORRECTED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE SET OF ALL OLD/VOIDED |
| | SHEETS ARE REQUIRED TO BE SUBMITTED |
| | SEPARATELY FOR REFERENCE. |
| | |
| | 3)NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS 3 OR MORE |
| | TIMES. THIS IS ONLY A NOTICE. |
| | |
| | 4)NOTE: PLEASE SEE ITEM NOT NOTED ON |
| | PREVIOUS REVIEW. PERMIT APPLICATION AND |
| | PLANS ARE REQUIRED TO CONTAIN THE SUITE/ |
| | UNIT NUMBER. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND ONCE AGAIN IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |