| Notes |
| Date |
Text |
| 2005-09-26 00:00:00 | MECH. RESUB PLAN REVIEW: | | | | | | MECH. PLAN REVIEW 08/10/05 PATTY | | | KRAUSS. | | | 1. AND 2. ITEMS O/K . | | | | | | 3. MUST BE ADHEARED TO.A/C SYSTEMS | | | COMBINED WITH OVER 2000 CFM REQUIR AUTO | | | FAN SHUT DOWN AND CONNECTED TO EXISTING | | | FIRE ALARM SYSTEM. 2001 FBC/M 606.2.1. | | | | | | 4. COND. UNIT SUPPORT STAND | | | INFORMATION, REQUIRED SIZE OF UNITS | | | AND WEIGHT CASAPITY OF STAND. 2003 FBC/M | | | 301.13 WIND RESISTANCE . | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | |
|