Plan Review Notes
Plan Review Notes For Permit 05080244
Permit Number 05080244
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-15 00:00:00************ UNSAT 2ND REVIEW*******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE PLANS ARE GOING TO BE
 COMING ABCK FOR MECH AND PLUMB COMMENTS.
 PLEASE SEE MECH AND PLUMB ARE NOT
 SIGNED, DATED OR SEALED, BY DESIGNER OF
 RECORD.
 PLEASE SEE PHOTO COPIES OF ORIGINALS.
 FS 471.025
  
  
 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLINGS,WHICH REQUIRES
 ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 2)NOTE: PLEASE BE SURE EXISTING RISER
 INDICATES WHICH BRKR/METER FEEDS NEW
 TENANT AND INDICATE OCP.
 215.5
 PLEASE KNOW, CONDUCTORS SHOWN CAN NOT BE
 VERIFIED AT THIS TIME.
 MORE THAN ONE BRKR IS BEING SHOWN IN
 METER CENTER, SOME 200A, 300A AND 400A.
  
  
 PLEASE BE SURE TO SEE ANY POSSILBE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF ALL REMOVED OLD/VOIDED SHEETS
 ARE REQUIRED TO BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]