| 2005-09-15 00:00:00 | ************ UNSAT 2ND REVIEW******* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE PLANS ARE GOING TO BE |
| | COMING ABCK FOR MECH AND PLUMB COMMENTS. |
| | PLEASE SEE MECH AND PLUMB ARE NOT |
| | SIGNED, DATED OR SEALED, BY DESIGNER OF |
| | RECORD. |
| | PLEASE SEE PHOTO COPIES OF ORIGINALS. |
| | FS 471.025 |
| | |
| | |
| | 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS |
| | IN OTHER THAN DWELLINGS,WHICH REQUIRES |
| | ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 2)NOTE: PLEASE BE SURE EXISTING RISER |
| | INDICATES WHICH BRKR/METER FEEDS NEW |
| | TENANT AND INDICATE OCP. |
| | 215.5 |
| | PLEASE KNOW, CONDUCTORS SHOWN CAN NOT BE |
| | VERIFIED AT THIS TIME. |
| | MORE THAN ONE BRKR IS BEING SHOWN IN |
| | METER CENTER, SOME 200A, 300A AND 400A. |
| | |
| | |
| | PLEASE BE SURE TO SEE ANY POSSILBE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF ALL REMOVED OLD/VOIDED SHEETS |
| | ARE REQUIRED TO BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |