| Plan Review Notes For Permit 05080244 |
| Permit Number |
05080244 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-10 00:00:00 | DENIED: | | | 1.PLAN SHEET AC-1, VERIFY & INDICATE | | | FIRE DAMPER FORTHE O.A. DUCT | | | PENETRATION PER 2001 FBC(M)607.1.2 7. | | | PROVIDE INSTALLATION DETAILS FOR FIRE | | | DAMPERS AS REQUIRED PER 2001 FBC(M) | | | 607.6.PLEASE NOTE, FIRE DAMPERS NOT | | | REQUIRED FOR DUCTS THAT COMPLY WITH 2001 | | | FBC(M)607.1.3 #3 ITEMS 1 THROUGH 4. | | | | | | 2.PLAN SHEET AC-1, DRYER EXHAUST DUCT | | | PENETRATING FLOOR INTO THE GARAGE AREA. | | | PLEASE PROVIDE INFORMATION AS TO THE | | | FIRE RATING FOR THE SEPARATION BETWEEN | | | OCCUPANCIES.PROVIDE FIRE PENETRATION | | | DETAIL. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE | | | REQUIRED FOR AHU-2.2001 FBC(M)606.2.1. | | | | | | 4.PROVIDE LOCATION OF THE CONDENSING | | | UNIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|