| Plan Review Notes For Permit 05080244 |
| Permit Number |
05080244 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-11 00:00:00 | ******DENIED****** | | | | | | 1) IN ADDITION TO THE FBC, LIFE SAFETY | | | TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 2) PLEASE SEE EXIT DOOR FROM EXECUTIVE | | | OFFICE SHALL NOT OBSTRUCT MORE THAN 1/2 | | | THE TOTAL CORRIDOR WIDTH DURING IT'S | | | SWING. PLEASE VERIFY. | | | | | | 3) PLEASE SHOW LOCATION OF 2A-10B,C | | | RATED FIRE EXTINGUISHER(S). IF EXISTING | | | IN COMMON AREAS, PLEASE ADVISE. | | | | | | 4) PLEASE INDICATE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR WALLS AND | | | CEILINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | FIRE PLAN REVIEW (561) 805-6722 |
|