2005-08-09 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE AS SHOWN.
 PLEASE SEE EM/EXT LTS, SEE 700.12E,THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 2)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLINGS,WHICH REQUIRES
 ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 3)NOTE: PLEASE SEE RISER INDICATES PANEL
 AS 225 2-P (MCB)? AND ALSO MLO. PLEASE
 CORRELATE. PLEASE SEE TEANT IS REQUIRED
 TO HAVE ACCESS TO ALL MEANS OF OCP.
 240.24
 215.5
  
 4)NOTE: PLEASE BE SURE EXISTING RISER
 INDICATES WHICH BRKR/METER FEEDS NEW
 TENANT AND INDICATE OCP.
 215.5
  
 PLEASE BE SURE TO SEE ANY POSSIBE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE SET OF ALL REMOVED OLD/VOIDED SHEETS
 ARE REQUIRED TO BE SUBMITTED FOR
 REFERENCE.
  