| 2005-09-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMIISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER |
| | REQUIRED IN THE TITLE BLOCK IS INDICATED |
| | AS NULL AND VOID AS OF 02/28/03 PER DBPR |
| | WEBSITE. SEE ATTACHED SHEET. - ALSO THE |
| | PRINTED NAME OF THE PERSON IS REQUIRED |
| | AS WELL AS THE DATED SEAL. FAC |
| | 61G1-16.004(5)(6) & FS 481.219 FS |
| | 481.2055. |
| | 2. SHT "1" OF 9 MINIMUM FACILITIES SHOWN |
| | DOES NOT INDICATE A DRINKING FOUNTAIN. |
| | PER TABLE 403.1, 3 DRINKING FOUNTAINS |
| | ARE REQUIRED. |
| | 3. SHT "7" OF 9 MINIMUM SCUPPER SIZE |
| | REQUIRED IS 22 SQ.IN. AND MINIMUM |
| | OPENING OF SCUPPERS IS 4" PER SECTION |
| | 1107.3. 2"X8" SCUPPER INDICATED IN |
| | DETAIL 1/5 IS NOT APPROVED. |
| | 4. SHT "7" OF 9 SUBMIT AN ISOMETRIC |
| | STORM RISER DIAGRAM SHOWING ALL PIPE |
| | SIZES AND INDICATE THE TERMINATION POINT |
| | FOR THE STORM FROM THE UPPER ROOF. SHOW |
| | THE SQUARE FOOTAGE AS IT ACCUMULATES IN |
| | THE STORM SYSTEM. SECTION 104.3.1.1. |
| | 5. SHT M-1 DRY HORIZONTAL VENTS ARE NOT |
| | APPROVED PER SECTIONS 905.3 & 905.4. |
| | 6. SUBMIT A FIXTURE SCHEDULE TO INDICATE |
| | THE NEW FIXTURES SHOWN ON FLOOR PLAN. |
| | SECTION 104.2.1. |
| | 7. SUBMIT A SANITARY RISER DIAGRAM AND A |
| | WATER RISER DIAGRAM IN ISOMETRIC FORM. |
| | SHOW ALL PIPE SIZES, TRAPS, VENTS ECT |
| | FOR THE SANT. SHOW ALL PIPE SIZES, |
| | VALVES, AND WATER HAMMER ARRESTORS, (IF |
| | REQUIRED BY SECTION 604.9), AND POINT OF |
| | CONNECTION. SECTION 104.3.1.1. |
| | 8. LANDSCAPE SHEETS SHALL BE SEALED BY |
| | THE LANDSCAPE ARCHITECT PER FAC |
| | 61G1-16.003 & FS 481.321(1) - THE |
| | CERTIFICATE OF AUTHORIZATION, (LANDSCAPE |
| | ARCHITECT BUSINESS LICENSE HAS BEEN NULL |
| | AND VOID SINCE 11/30/95 PER DBPR RECORDS |
| | AND SHALL BE UPDATED PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. THE |
| | CA # IS REQUIRED PER FAC 61G1-16.004(2) |
| | AND FS 481.319. |
| | |
| | REVIEW BY KEN STEVENS |