2005-08-11 00:00:00IN ELEC FOR REVIEW
 *********** UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL NEW CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE ALSO SHOW EXHAUST FANS ON
 ELECTRICAL PLANS.
 215.5
  
 2)NOTE: PLEASE CORRELATE NOTES TO
 ELECTRICLA PLANS, PANEL SCHEDULE AND
 PLANS, NOTES MENTION 250A PANEL MIN AND
 OTHERS 225A?
 215.5
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 SHOWING WHERE NEW PANEL IS BEING FED
 FROM, SIZE OF EXISTING PANEL/DISCONNECT/
 SERVICE.
 PLEASE SUBMIT LOAD CALCULATIONS FOR
 ADDITION OF NEW LOADS TOEXISTING
 SERVICE.
 220.3,220.10,220.11,220.13 ETC.
 PLEASE SEE THAT ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE ALL EM/EXT LTS ARE TO
 BE CIRCUITED PER 700.12E, WHICH REQUIRES
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 5)NOTE: PLEASE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL TO EXIST
 ,,
 PLEASE SEE "NOTES" MENTION A 2/0 FOR
 EQUIPMENT GROUNDING? PLEASE VERIFY THIS.
 250.110,250.122,250.24
  
 6)NOTE: PLEASE SEE NOTE TO PANEL
 MENTIONS: ALL WORK PER NEC AND "COUNTY
 CODES", PLEASE SEE THIS JOB IS LOCATED
 IN THE CITY OF WEST PALM BEACH AND PLANS
 SHOULD NOTE CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS.
  
 7)NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK PER FAC
 61G1-16.004.
 PLEASE SEE MISSING THE PRINTED NAME AND
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 ON ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 ********
 PLEASE SEE COMMENTS FROM BLDG REVIEW
 ALSO, PLEASE SEE SURVEY IS REQUIRED TO
 HAVE AN ORIGINAL SIGNATURE BY THE PERSON
 SEALING SURVEY PLANS.
 PLEASE SEE FS 472.025
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]