| 2005-08-11 00:00:00 | IN ELEC FOR REVIEW |
| | *********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SHOW ALL NEW CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULE. |
| | PLEASE ALSO SHOW EXHAUST FANS ON |
| | ELECTRICAL PLANS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE CORRELATE NOTES TO |
| | ELECTRICLA PLANS, PANEL SCHEDULE AND |
| | PLANS, NOTES MENTION 250A PANEL MIN AND |
| | OTHERS 225A? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM |
| | SHOWING WHERE NEW PANEL IS BEING FED |
| | FROM, SIZE OF EXISTING PANEL/DISCONNECT/ |
| | SERVICE. |
| | PLEASE SUBMIT LOAD CALCULATIONS FOR |
| | ADDITION OF NEW LOADS TOEXISTING |
| | SERVICE. |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE SEE THAT ALL CONTINUOUS LOADS AND |
| | LARGEST MOTOR LOADS ARE SHOWN AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 4)NOTE: PLEASE SEE ALL EM/EXT LTS ARE TO |
| | BE CIRCUITED PER 700.12E, WHICH REQUIRES |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 5)NOTE: PLEASE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM PANEL TO EXIST |
| | ,, |
| | PLEASE SEE "NOTES" MENTION A 2/0 FOR |
| | EQUIPMENT GROUNDING? PLEASE VERIFY THIS. |
| | 250.110,250.122,250.24 |
| | |
| | 6)NOTE: PLEASE SEE NOTE TO PANEL |
| | MENTIONS: ALL WORK PER NEC AND "COUNTY |
| | CODES", PLEASE SEE THIS JOB IS LOCATED |
| | IN THE CITY OF WEST PALM BEACH AND PLANS |
| | SHOULD NOTE CITY OF WEST PALM BEACH |
| | LOCAL AMENDMENTS. |
| | |
| | 7)NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION ON TITLE BLOCK PER FAC |
| | 61G1-16.004. |
| | PLEASE SEE MISSING THE PRINTED NAME AND |
| | LICENSE NUMBER FOR ARCHITECT OF RECORD. |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | ON ALL SHEETS AND FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | ******** |
| | PLEASE SEE COMMENTS FROM BLDG REVIEW |
| | ALSO, PLEASE SEE SURVEY IS REQUIRED TO |
| | HAVE AN ORIGINAL SIGNATURE BY THE PERSON |
| | SEALING SURVEY PLANS. |
| | PLEASE SEE FS 472.025 |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE |
| | REMOVED FROM SETS AND INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |