| Date |
Text |
| 2005-12-14 00:00:00 | |
| | |
| | ***NOTE*** LETTER SUBMITTED FROM |
| | ARCHITECT & OWNER REGARDING OCCUPANCY, |
| | NMK DETERMINED THAT OCCUPANCY IS "F" |
| | |
| 2005-08-29 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | |
| | 1.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 |
| | |
| | 2.)THE SHEETS PREPARED BY THE |
| | LANDSCAPE ARCHITECT ARE TO BE SIGNED, |
| | SEALED AND DATED FAC61G10-11.010(2). |
| | |
| | 3.)THE ARCHITECT?S TITLE BLOCK IS TO |
| | COMPLY WITH FAC61G1-16-003,004.THE |
| | SEAL IS TO BE DATED. |
| | |
| | 4.)THE OWNER ON THE APPLICATION |
| | CONFLICTS WITH OUR RECORDS. |
| | |
| | 5.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 6.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 7.)DECLARE AN OCCUPANCY FOR THE |
| | EXISTING BUILDING AND THE ADDITION, |
| | FBC305, FBC307.THE NOTE ON THE PLAN |
| | STATING ?NO OPERATIONAL EQUIP IN |
| | PROPOSED ADDITION? IS ACKNOWLEDGED.THE |
| | ROOM LABEL CALLS THIS ROOM AN WELDING & |
| | PIPEFITTING LABORATORY; IF THERE IS NO |
| | OPERATIONAL EQUIPMENT, WHAT TYPE OF |
| | LABORATORY IS IT?THERE ARE 220 OUTLETS |
| | ON THE ELECTRIC PLAN, EXHAUST FANS ON |
| | THE ROOF FRAMING PLAN, AND SHEET M1 |
| | LABELS THIS ROOM AS A WELDING AND |
| | PIPEFITTING SHOP. |
| | |
| | 8.)SHOW OCCUPANCY SEPARATION REQUIRED |
| | BY FBC TABLE 704.1. |
| | |
| | 9.)NOTE THAT IF THIS IS F OCCUPANCY, |
| | TWO EXITS REQUIRED. |
| | |
| | 10.)PROVIDE INFORMATION IN REGARDS TO |
| | THE EXISTING BUILDING; MINIMUM BUILDING |
| | TYPE, HEIGHT (NUMBER OF STORIES), |
| | PROTECTED OR UNPROTECTED, SPRINKLED OR |
| | UNSPRINKLED, OCCUPANCY. |
| | |
| | 11.)THE PRODUCT APPROVALS SUBMITTED |
| | FOR THE ROOF WERE FOR A ROOF DECK.THE |
| | DETAILS SHOW LIGHTWEIGHT CONCRETE. |
| | |
| | 12.)SUBMIT PRODUCT APPROVALS FOR THE |
| | OVERHEAD DOORS, EXTERIOR DOOR, ROOF |
| | VENT. |
| | |
| | 13.)THE FLOOR PLAN SHOWS AN ADDITION, |
| | OPEN PRACTICE AREA.THIS DOES NOT |
| | APPEAR ON THE OTHER SHEETS.NOTE THAT |
| | IT ALSO DOES NOT SHOW A DOOR.CLARIFY |
| | THE SCOPE OF WORK. |
| | |
| | 14.)PROVIDE A DETAIL FOR THE |
| | MECHANICAL EQUIPMENT ON THE ROOF, FBC |
| | 1511.7. |
| | |