Text |
| 2006-10-17 14:59:06 | CONTRACTOR CALLED, | | | REMOVED OLD E-2, AS THIS RISER DOES NOT APPLY. | | | | | | RISERGROUNDING ELECTRODE CONDUCTOR NEEDS TO BE SIZED | | | PER 250.66. THIS APPEARS IT SHOULD BE 2/0. |
|