| Date |
Text |
| 2006-06-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | MUNICIPAL CODE |
| | |
| | 1. SUBMIT A SANITARY RISER DIAGRAM AND |
| | PLAN VIEW OF THE PIPING. SHOW ALL PIPE |
| | SIZES, VENTS, TRAPS ETC. SECTION |
| | 104.3.1.1. |
| | |
| | 2. SUBMIT A WATER RISER DIAGRAM AND PLAN |
| | VIEW OF THE PIPING. SHOW ALL PIPE SIZES, |
| | VALVES AND WATER HAMMER ARRESTORS IF |
| | REQUIRED BY SECTION 604.9. SECTION |
| | 104.3.1.1. |
| | |
| | 3. A GREASE INTERCEPTOR MAY BE REQUIRED |
| | AND IF SO, A GREASE WASTE SYSTEM WILL BE |
| | REQUIRED FOR THE KITCHEN. PLEASE CONTACT |
| | LYNN MASSON ENVIRONMENTAL COMPLIANCE FOR |
| | A DERTIMINATION. HER PHONE NUMBER IS |
| | (561) 822-2271, FAX (561 822-2279, AND |
| | E-MAIL [email protected]. MUNICIPAL CODE |
| | SECTION #3434. |
| | |
| | 4. THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE SEPARATE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. (LENGTHS FOR EACH CUT |
| | SECTION NOT SHOWN). |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | (NO RESPONSE, NOT ADDRESSED). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). (NO RESPONSE, |
| | NOT ADDRESSED) |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. (NEEDS TO |
| | BE SHOWN ON THE GAS RISER ISOMETRIC). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |