| Date |
Text |
| 2005-12-21 00:00:00 | ************* UNSAT *************** |
| | |
| | PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| | STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE CHANGES IN ELECTRICAL |
| | RISER ALONG WITH PLANS STILL SHOWING |
| | OTHER NEED TO BE ADDRESSED. |
| | |
| | *** PLEASE KNOW, WHEN PLANS WERE |
| | SUBMITTED BACK TO THE CONSTRUCTION |
| | SERVICES DEPT. ON OCT 12, 2005, "ONLY" |
| | THE OLD/ UN-CORRECTED PLANS WERE |
| | SUBMITTED BACK FOR REVIEW AND NO "NEW" |
| | OR REVISED PLANS WERE SUBMITTED. THIS IS |
| | THE REASON WHY FIRE AND ELECTRICAL |
| | REVIEW HAD A 2ND REVIEW WHICH REFERENCED |
| | TO THE SAME COMMENTS FROM ORIGINAL |
| | REVIEW. |
| | ** PLEASE KNOW THAT THE NEW/REVISED |
| | PLANS NOT SUBMITTED BACK ON OCT 12, WERE |
| | ALLOWED TO BE BROUGHT IN ON NOV 21ST, |
| | 2005 TO BE RE-REVIEWED. THESE PLANS WERE |
| | BROUGHT IN BY MR. KEVIN BUTLER II. |
| | I HOPE THIS CLEARS UP ANY CONFUSION OVER |
| | WHY THERE WAS REFERENCE TO OLD/PLANS. |
| | |
| | PLEASE SEE THE FOLLOWING: |
| | |
| | ** NOTES TAKEN DIRECTLY FROM FIRST |
| | REVIEW. |
| | |
| | 1)NOTE:NOTE #1, NO. PLEASE SEE FIRST |
| | PART OF NOTE MENTIONED TO SHOWALL |
| | CIRCUITING NEWAND CORRELATE WITH |
| | SUBMITTED PANEL SCHEDULE(S). |
| | THIS WAS DONE, HOWEVER PLEASE SEE THIS |
| | NOTE AND NOTE #2 REQUESTED ALLEM/EXT |
| | LTS TO BE CIRCUITED TO THE LOCAL BRANCH |
| | CIRCUIT FEEDING UNIT EQUIPMENT.THIS WAS |
| | DONE FOR EM LTS, HOWEVER NOT THE EXT |
| | LTS. |
| | PLEASE ADJUST CIRCUITING. |
| | |
| | |
| | 2)NOTE: NOTE #2,YES/NO PLEASE SEE THAT |
| | BATTERY BACK UP EXIT LTS WERE ADDED FOR |
| | LIGHTING THE EGRESS PATH TO EXIT |
| | DISCHARGE, HOWEVER COULD NOT LCOATE ANY |
| | INFORMATION WITH RESPECT TO NOTES OR MIN |
| | FT CANDLES REQUIRED. PLEASE SEE NFPA-101 |
| | 7-8, WHICH REQUIRES THE MEANS OF EGRESS |
| | LIGHTING TO MEET AMIN OF 10 FT CANDLES |
| | DURING NORMAL POWERE AND A MIN OF 1 FT |
| | CANDLE DURING EMERGENCY CONDITIONS( LOSS |
| | OF NORMAL POWER). |
| | PLEASE PROVIDE AT A MININUM, NOTING FOR |
| | THESE MIN REQUIREMENTS. |
| | PLEASE SEE 2003 NFPA-101 7.8, 7.9 |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK. (ONLY NOTED) |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE A NOTE |
| | WAS ADDED MENTIONING "WHEN REQUIRED" |
| | PLEASE SEE FIRE/MECHANCICAL REVIEW |
| | NOTES, A "SHUNT TRIP" OF SOME SORT WOULD |
| | BE REQUIRED TO SHUT DOWN ALL ELECTRICAL |
| | IN A HOOD AREA. |
| | PLEASE PROVIDE REFERENCE TO NFPA-96 WITH |
| | MEANS OF SHUT DOWN OF ANY |
| | ELECTRICAL DEVICES UNDER HOOD. |
| | PLEASE SEE CHAPTERS 9 AND 10 |
| | |
| | 7)NOTE: NOTE #7 OK, A DOOR AND WALL WERE |
| | ADDED TO SEPARATE FROM STORAGE AREA OF |
| | CLOSET. |
| | |
| | 8)NOTE: NOTE #8, OK. |
| | |
| | 9)NOTE: NOTE #9, NO PLEASE SEE |
| | 250.6,250.24, "EQUIPMENT GROUNDING " |
| | CONDUCTORS ARE ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE THESE "EQIPMENT GROUNDING |
| | CONDUCTORS"ARE STILL BEING SHOWN , |
| | BOTH ON REFERENCE TO THE EXISTING SEC'S |
| | AND TO THE NEW SEC'S. |
| | PLEASE SEE NEW COMMENTS WITH RESPECT TO |
| | THE SERVICE. |
| | PLEASE SEE EQP GRND FROM METER TO |
| | MAIN.(NEW)AND EXISTING. |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 NO/YES, PLEASE SEE THE |
| | TAPS FOR NEW MAIN IS NOW SHOWN, HOWEVER |
| | PLEASE SEE NEW NOTE ADDING A TAP TO |
| | EXISTING MAIN WILL NOT BE PERMITTED. |
| | PLEASE ALSO KNOW, PREVIOUS COMMENT |
| | REQUESTED OF THIS WAS A NEW SERVICE OR |
| | COMING FROM THE EXISTING SERVICE RISER? |
| | PLEASE SEE RISER NOW INDICATES THIS TAP |
| | LOCATED IN "CT" AND DOES NOT SHOW A NEW |
| | RISER OR SEC'S UP TO A NEW WEATHER HEAD. |
| | THERFORE, PLEASE SHOW EXISTING SEC'S IN |
| | RISER AND PLEASE BE SURE TO MAKE SURE |
| | THE EXISTING SIZE IS ADEQUATE FOR BOTH |
| | NEW AND EXISITNG. PLEASE SEE EXISITNG IS |
| | SHOWN AS 600A'S AND NEW MAIN IS 400'S. |
| | PLEASE SEE 230.2 FOR NEW |
| | SERVICE AS SHOWN ON PLANS. PLEASE |
| | CLARIFY IF "NEW SERVICE" IS GOING TO BE |
| | FED FROM THE SAME SERVICE DROP AND |
| | TRANSFORMER. |
| | *** PLEASE SEE PLANS STILL INDICATE |
| | THERE BEING A "NEW METER", AN "EXISITNG |
| | METER" AND AND "EXISITNG CT" WHICH DOES |
| | NOT CORRELATE WITH THE RISER DIAGRAM |
| | SHOWN FOR SERVICE. |
| | PLEASE CORRELATE THE ABOVE AND CALL TO |
| | GO OVER OPTIONS IF NEEDED. |
| | 215.5 |
| | |
| | ** NEW NOTE: |
| | |
| | 1)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| | PROFESSIONAL AND REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. |
| | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN |
| | AT THIS TIME. |
| | ONE COPY OF ELECTRICAL PLANS ARE BEING |
| | RETAINED. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS ARE |
| | REQUIRED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-12-20 00:00:00 | IN ELEC FOR REVIEW. |
| | THIS REVIEW IS BEING DONE ON THE "NEW" |
| | PLANS SUBMITTED ON NOV 21ST, 2005. |
| | |
| | SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED, AND COMMENTS DUE |
| | TO INFORMATION ADDED TO PLANS. |
| | NOTES TO FOLLOW, REVIEW IN PROGRESS. |