| Date |
Text |
| 2006-01-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | A. PREVIOUS COMMENTS FROM FIRST REVIEW |
| | NOT ADDRESSED. COMMENT NUMBERS TO REMAIN |
| | THE SAME AS FIRST REVIEW: |
| | |
| | 1. INDICATE AGE OF STUDENTS TO DETERMINE |
| | THE OCCUPANCY. SECTION 104.2.1. (NOT |
| | ADDRESSED, NO RESPONSE). PLEASE INDICATE |
| | OCCUPANCY AND INDICATE AGE OF STUDENTS. |
| | 2. ROUTE PLANS TO THE PALM BEACH HEALTH |
| | UNIT DIVISION OF ENVIRONMENTAL HEALTH |
| | FOR REVIEW PRIOR TO RESUBMITTING FOR |
| | PLAN REVIEW AT THE CITY WPB. SECTION |
| | 101.4.7. (NO RESPONSE, NOT ADDRESSED). |
| | 4. SHT A-6 SHOW THE FOLLOWING TO SHOW |
| | COMPLIANCE OF THE ACCESSIBILITY CODE: |
| | FOR LAVS... |
| | 11-4.19.5 FAUCETS |
| | TOILET ROOM: |
| | 11-4.22.3 TURNING AREA IN TOILET ROOM, |
| | NOT IN THE STALL. |
| | 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS |
| | AN ARCHITECT OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THIS STATE |
| | REGULATING THE PRACTICE OF ARCHITECTURE |
| | OR ENGINEERING, THEN HE/SHE SHALL AFFIX |
| | HIS/HER OFFICIAL SEAL TO SAID DRAWINGS, |
| | AS REQUIRED FY FLORIDA STATUTES. SECTION |
| | 104.2.2. (SHEETS A-1, A-4,A-7, & S-1 NOT |
| | SIGNED, SEALED, DATED) |
| | 8. THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE SEPARATE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. (LENGTHS FOR EACH CUT |
| | SECTION NOT SHOWN). |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | (NO RESPONSE, NOT ADDRESSED). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). (NO RESPONSE, |
| | NOT ADDRESSED) |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. (NEEDS TO |
| | BE SHOWN ON THE GAS RISER ISOMETRIC). |
| | |
| | **************NEW COMMENT*************** |
| | 1B. SEE ATTACHED SHEET CONCERNING FS |
| | 553.80(2)(B) AND THE DESIGN |
| | PROFESSIONAL. (ATTACHED TO ELECTRICAL |
| | COMMENTS). THIS IS GIVEN AS A NOTICE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |