| 2005-12-25 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | |
| | 1.)FROM PREVIOUS REVIEW, #4.PROVIDE |
| | INFORMATION IN REGARDS TO |
| | THE EXISTING BUILDING; MINIMUM BUILDING |
| | TYPE, HEIGHT (NUMBER OF STORIES), |
| | PROTECTED OR UNPROTECTED, SPRINKLED OR |
| | UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE |
| | 500 COMPLIANCE CAN BE DETERMINED. |
| | |
| | PLEASE PROVIDE ALL INFORMATION |
| | REQUESTED.SHOW COMPLIANCE WITH FBC |
| | TABLE 500 AS REQUESTED ON FIRST REVIEW. |
| | THIS IS TYPICALLY DONE IN A CODE SUMMARY |
| | SECTION.SOME INFORMATION WAS PROVIDED |
| | BUT NOT ENOUGH TO DETERMINE CODE |
| | COMPLIANCE.FOR INSTANCE, WHETHER OR |
| | NOT THE BUILDING IS SPRINKLED WAS NOT |
| | DECLARED ON THE PLAN.THE OCCUPANCY |
| | CLASSIFICATION AND SUBCLASSIFICATION WAS |
| | NOT DECLARED, PROTECTED OR UNPROTECTED. |
| | IT APPEARS TO BE ONE STORY, PLEASE |
| | DECLARE SO ON THE PLAN. |
| | |
| | 2.)SEE FBC503.1.2.YOU SHOW A PORTION |
| | OF THE BUILDING AS TYPE V, ANOTHER |
| | PORTION AS TYPE III.FOR A BUILDING TO |
| | BE DECLARED TWO DIFFERENT BUILDING |
| | TYPES, A FIRE WALL BETWEEN THE TWO |
| | BUILDING TYPES IS REQUIRED.SHOW |
| | EXISTING OR PROPOSED FIRE WALL AND |
| | PROVIDE A DETAIL.PROVIDE INFORMATION |
| | IN REGARDS TO EXISTING CONSTRUCTION SO |
| | THAT THE BUILDING TYPE DECLARED CAN BE |
| | CONFIRMED. |
| | |
| | 3.)IF THIS IS TWO BUILDINGS AS DEFINED |
| | BY FBC503.1.2, PROVIDE TOTAL AREA OF |
| | EACH BUILDING TYPE SO THAT TABLE 500 |
| | COMPLIANCE CAN BE DETERMINED. |
| | |
| | 4.)IF THIS ENTIRE BUILDING IS ACTUALLY |
| | A TYPE V BUILDING, SEE FBC TABLE 500. |
| | AN UNSPRINKLED TYPE V A2 BUILDING IS |
| | RESTRICTED TO A SIZE OF 8000 SF.THIS |
| | BUILDING IS OVER 13,000 AND YOU ARE |
| | PROPOSING TO ADD 200 SF.THE ADDITION |
| | AS PRESENTED DOES NOT APPEAR CODE |
| | COMPLIANT BUT NOT ENOUGH INFORMATION WAS |
| | PROVIDED TO MAKE THIS DETERMINATION. |
| | |
| | 5.)DECLARE GOVERNING CODE.IF YOU ARE |
| | DESIGNING UNDER THE FBC2004, PLEASE |
| | ADVISE SO THAT I CAN REVISE CODE |
| | REFERENCE NUMBERS IF NECESSARY. |
| | COMMENTS STILL APPLY. |
| | |
| | 6.)IF YOU ARE DESIGNING UNDER FBC2004, |
| | PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | THE DESIGNER OF RECORD, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO THE FBC2004 |
| | 106.3.3. |
| | |
| | 7.)FROM PREVIOUS REVIEW, ITEM #8. |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVALS |
| | REQUIRED FOR THE ROOF AND THE WINDOW. |
| | PROVIDE BOTH THE STATE OR LOCAL PRODUCT |
| | APPROVAL AND THE CORRESPONDING |
| | EVALUATION OR TEST REPORT AND |
| | INSTALLATION INSTRUCTIONS.THE |
| | RESPONSE LETTER FROM THE ARCHITECT |
| | STATES THAT THE WINDOWS ARE EXISTING AND |
| | NOT BEING REPLACED.THERE IS A NEW |
| | WINDOW SHOWN AT THE SINK IN THE KITCHEN |
| | ADDITION.PRODUCT APPROVAL FOR THE ROOF |
| | WERE NOT SUBMITTED. |
| | |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.)IMPACT PROTECTION REQUIRED FOR THE |
| | WINDOW FBC1606.1.4.IF YOU PROPOSE |
| | USING REMOVABLE SHUTTERS, APPROVAL BY |
| | THE BUILDING OFFICIAL IS REQUIRED.SEE |
| | ATTACHED POLICY, ITEM 13. |
| | |
| | 8.)SHEETS A1, A4, A7, S1 ARE NOT |
| | SEALED.DOCUMENTS PREPARED BY AN |
| | ARCHITECT AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED, SEALED, AND |
| | DATED ORIGINALS.FAC61G1-16. |
| | |
| | 9.)THE NOA SUBMITTED IS EXPIRED, OVER |
| | 90 DAYS WITHOUT COMMENCING WORK, |
| | FS713.13(2). |
| | |
| | 10.) SHOW TURNING RADIUS IN BATHROOM, |
| | FBC11-4.22.3. |
| | |
| | 11.) SPECIFY HURRICANE STRAPS AND SHOW |
| | DESIGN CRITERIA, SHEET A7. |
| | |
| | 12.) SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW IS REQUIRED TO BE CHARGED IF |
| | THE CORRECTIONS ARE NOT PROPERLY |
| | ADDRESSED IN THE THIRD REVIEW. |