| Notes |
| Date |
Text |
| 2005-09-06 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE THAT REQUIRED MEANS OF | | | EGRESS MUST BE CLEARLY MARKED. PLEASE | | | SHOW LOCATIONS OF ALL ILLUMINATED EXIT | | | SIGNS AND EMERGENCY LIGHTING FACILITIES | | | IN AREAS DIRECTING PERSONS TO AN EXIT | | | AND EXIT DISCHARGE. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED TO SATISFY | | | THE 75' TRAVEL DISTANCE REQUIREMENT. | | | PLEASE SHOW IF EXISTING OR NEW. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND | | | FIRER ALARM REMODEL IF APPLICABLE. | | | | | | 4) NO COOKING OF FOODS THAT PRODUCE | | | GREASE LADEN VAPORS UNLESS PROTECTED BY | | | APPROVED HOOD AND SUPPRESSION SYSTEMS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|