| Date |
Text |
| 2005-08-15 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING FOR |
| | NEWAND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULE(S). |
| | PLEASE SEE EXT/ EM LT PER 700.12E,THE |
| | BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | |
| | 2)NOTE: PLEASE SEE NFPA-101 7-8, WHICH |
| | REQUIRES MEANS OF EGRESS LIGHTING TO THE |
| | EXIT DISCHARGE/ TO PUBLIC RIGHT OF WAY. |
| | PLEASE SEE CORRIDORS IN OPEN COURTYARD |
| | AREAS. 101,15.2 |
| | PLEASE ALSO SEE 700.12E FOR CIRCUITINGOF |
| | EM/LTS.PREVIOUSLY NOTED. |
| | |
| | 3)NOTE: PLEASE SEE 2002 NEC FOR |
| | PROTECTION OF RECEPTS IN KITCHENS IN |
| | OTHER THAN DWELLING UNITS, WHICH |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 4)NOTE: PLEASE SEE MISSING THE "PRINTED" |
| | LICENSE NUMBER OF THE ENGINEER OF |
| | RECORD. PLEASE SEE FAC 61G15-23.002 |
| | FS 471 |
| | |
| | 5)NOTE: PLEASE SEE BLDG, ZOING COMMENTS, |
| | NO SURVEY/SITE PLAN SHOWING SETBACKS FOR |
| | NEW KITCHAN ADDITION WAS SUBMITTED. |
| | PLEASE SEE FS 472.025, FAC 61G17-7.002, |
| | PLEASE BE SURE ALL SURVEY'S CONTAIN THE |
| | ABOVE. |
| | |
| | 6)NOTE: PLEASE PROVIDE REFERENCE TO |
| | NFPA-96 WITH MEANS OF SHUT DOWN OF ANY |
| | ELECTRICAL DEVICES UNDER HOOD. |
| | PLEASE SEE CHAPTERS 9 AND 10 |
| | |
| | 7)NOTE: PLEASE SEE PANEL "B" WHICH IS |
| | SHOWN AS EXISTING SHALL NOT BE LOCATED |
| | IN "OFFICE CLOSET". PLEASE SEE FIRE |
| | REVIEW NOTES, NO STORAGE PERMITTED IN |
| | SPACES ABOUT ELECTRICAL EQUIPMENT/RMS. |
| | PLEASE SEE 408.7,240.24D, 110.26 ETC |
| | PLEASE SEE THIS AREA FOR LOCATION OF |
| | PANEL NEEDS TO REFERENCE, ELEC/MECH RM. |
| | |
| | 8)NOTE:PLEASE CLARIFY/ SHOW EITHER NEW |
| | OR EXISTING ROOF-TOP WP GFI RECEPTS FOR |
| | RTU'S PER 210.63 |
| | |
| | 9)NOTE: PLEASE SEE 250.6,250.24, |
| | "EQUIPMENT GROUNDING " CONDUCTORS ARE |
| | ONLY INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | PLEASE SEE EQP GRND FROM METER TO |
| | MAIN.(NEW). |
| | |
| | 10)NOTE: PLEASE SHOW METHOD OF EQUIPMENT |
| | GROUNDING FROM PANELS TO ALL RTU'S. |
| | PLEASE KNOW, EMT MAY ONLY BE USED AS AN |
| | "EQUIPMENT GROUND PATH" IF USED IN |
| | CONNECTION WITH NEW "LISTED" EQUIPMENT |
| | GROUNDING CONNECTORS AND COUPLINGS. |
| | 110.3 |
| | |
| | 11)NOTE: PLEASE SEE 230.2 FOR NEW |
| | SERVICE AS SHOWN ON PLANS. PLEASE |
| | CLARIFY IF "NEW SERVICE" IS GOING TO BE |
| | FED FROM THE SAME SERVICE DROP AND |
| | TRANSFORMER. |
| | 215.3 |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS ARE |
| | REQUIRED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |