| Plan Review Notes For Permit 05080171 |
| Permit Number |
05080171 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-07 00:00:00 | DENIED:2ND REQUEST | | | COMMENT #2 FROM REVIEW DATED 8/22/05 | | | | | | RETURN AIR SHALL COMPLY WITH 2001 FBC(M) | | | 601.4, RETURN SHALL BE EQUAL TO THE | | | SUPPLY AIR FOR A BALANCED SYSTEM. | | | | | | THE ROOM BETWEEN THE COMPUTER TELE EQUIP | | | & SAFTEY ROOM INDICATES A 12" SUPPLY ON | | | PLAN SHEET M-1 BUT INDICATES ONLY A 6" | | | RETURN.PLEASE VERIFY ALL OFFICE AREAS | | | FOR COMPLIANCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|