2005-09-07 00:00:00DENIED:2ND REQUEST
 COMMENT #2 FROM REVIEW DATED 8/22/05
  
 RETURN AIR SHALL COMPLY WITH 2001 FBC(M)
 601.4, RETURN SHALL BE EQUAL TO THE
 SUPPLY AIR FOR A BALANCED SYSTEM.
  
 THE ROOM BETWEEN THE COMPUTER TELE EQUIP
 & SAFTEY ROOM INDICATES A 12" SUPPLY ON
 PLAN SHEET M-1 BUT INDICATES ONLY A 6"
 RETURN.PLEASE VERIFY ALL OFFICE AREAS
 FOR COMPLIANCE.
  