Plan Review Notes
Plan Review Notes For Permit 05080171
Permit Number 05080171
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-22 00:00:00DENIED:
 1.PLEASE INDICATE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) TABLE
 403.3.
  
 2.PLEASE INDICATE ALL RETURN AIR DUCT
 & DIFFUSERS.PLEASE NOTE THE FOLLOWING
 ROOMS DO NOT INDICATE R/A; LARGE
 CONFERENCE RM, BREAK RM, ASSISTANT
 PARTNER RM, 2 NEW OFFICE RMS, ACCOUNTANT
 RM, SAFETY & OFFICE NEXT TO SAFETY RM.
 PER 2001 FBC(M)601.4, BALANCED AIR
 REQUIRED.
  
 3.PLEASE NOTE, SHOULD A/C EXCEED 2,000
 CFM (5 TON & GREATER), FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR WILL BE REQUIRED PER
 2001 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  