| Plan Review Notes For Permit 05080171 |
| Permit Number |
05080171 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-22 00:00:00 | DENIED: | | | 1.PLEASE INDICATE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) TABLE | | | 403.3. | | | | | | 2.PLEASE INDICATE ALL RETURN AIR DUCT | | | & DIFFUSERS.PLEASE NOTE THE FOLLOWING | | | ROOMS DO NOT INDICATE R/A; LARGE | | | CONFERENCE RM, BREAK RM, ASSISTANT | | | PARTNER RM, 2 NEW OFFICE RMS, ACCOUNTANT | | | RM, SAFETY & OFFICE NEXT TO SAFETY RM. | | | PER 2001 FBC(M)601.4, BALANCED AIR | | | REQUIRED. | | | | | | 3.PLEASE NOTE, SHOULD A/C EXCEED 2,000 | | | CFM (5 TON & GREATER), FAN SHUTDOWN BY | | | DUCT SMOKE DETECTOR WILL BE REQUIRED PER | | | 2001 FBC(M)606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|