Plan Review Notes
Plan Review Notes For Permit 05080171
Permit Number 05080171
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-12 00:00:00***** UNSAT *******
  
 1)NOTE: PLEASE COMPLETE AND SHOW ALL
 CIRCUITING ON PLANS AND CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULE.
 PLEASE SEE SOME ITEMS/DEVICES ON PLANS
 WITH NO CIRCUITING.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
 PLEASE COMPLETE CONTROL/CIRCUITING OF
 LTS ON PLANS. PLEASE SEE SOME OF LTS
 SHOWN DO NOT INDICATE ANY MEANS OF
 CONTROL OR CIRCUITING.
 215.5
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER 220.3, 220.10, 220.11,
 220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOADS ON PANEL AND PANEL IS
 SHOWN AS "BLANK".
  
 3)NOTE: PLEASE INDICATE WHERE PANEL IS
 BEING FED FROM, PLEASE SHOW LOAD ON
 EXISTING SERVICE FOR NEW 400A PANEL,
 PLEASE SEE PREVIOUS NOTE #2.
 PLEASE INDICATE FEEDERS, GROUNDING, ETC
 ON A RISER DIAGRAM.
  
 4) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 5)NOTE: PLEASE INDICATE NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 6)NOTE: PLEASE SEE ALL RECEPTS WITH IN
 6' OF SINKS SHALL BE SHOWN AS GFI.210.8
 PLEASE SEE GFI PROTECTION REQUIRED FOR
 ALL RECEPTS IN KITCHEN AREAS IN OTHER
 THANDWELLING UNITS. PLEASE SEE 210.8B3
  
 WHICHREQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 PLEASE BE SURE TO SEE ANY OTHER COMMENTS
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS REVIEW
 561-805-6717
 [email protected]
  
  