Plan Review Notes
Plan Review Notes For Permit 05080168
Permit Number 05080168
Review Stop E
Sequence Number 5
Notes
Date Text
2007-03-15 12:06:09** UNSAT**
  
 1) NOTE: PLEASE SEE AS STATE IN PREVIOUS REVIEW THE
 MINIMUM LEVELS FOR ADA COMPLIANCE MUST BE STATED ON
 THESE PLANS PER FBC 2001 11-4.28.1,.2,.3(4).
  
 PLEASE SEE THAT THE PERMIT FOR THE FIRE ALARM SYSTEM
 HAS NOT BEEN ADJUSTED AND SHALL REMAIN IN A HOLD STATUS
 AND NO INSPECTIONS CAN BE DONE.
 PLEASE SEE THE PREVIOUS COMMENTS WITH RESPECT TO THE
 VALUATION OF THIS SCOPE OF WORK.
 PLEASE SEE THERE ARE FEES OWED ON THE SECURITY PERMIT
 AND NEED TO BE PAID ALSO.
 FBC 106.3.5 (2001) 108.3(2004). VALUATION SHALL INCLUDE
 ALL LABOR AND MATERIALS WHETHER OR NOT ANY EQUIPMENT OR
 MATERIALS ARE OWNER SUPPLIED.
 ANY CONTRACT/MONATERING VALUE SHALL ALSO BE INCLUDED
 (WHERE APPLICABLE).
  
 AT THIS TIME THE ELECTRICAL, FIRE ALARM AND LOW VOLTAGE
 SECURITY PERMIT WILL BE PLACED ON HOLD.
  
 *
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  