| Plan Review Notes For Permit 05080168 |
| Permit Number |
05080168 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-03 00:00:00 | ******DENIED****** | | | | | | IT DOES NOT APPEAR THAT THE COMMENTS | | | FROM THE LAST REVIEW HAVE BEEN | | | ADDRESSED. | | | | | | | | | 1) SHT E-101 SHOWS FIRE ALARM EQUIPMENT. | | | IS THIS NEW OR EXISTING? PLEASE INDICATE | | | IF FIRE ALARM AND FIRE SPRINKLER SYSTEMS | | | ARE PART OF THE SCOPE OF THIS WORK. | | | | | | 2) DUCT SMOKE DETECTORS SHALL BE | | | INSTALLED IN SUPPLY AIR SYSTEM WHERE | | | CAPACITY IS GREATER THAN 2000 CFM. | | | | | | 3) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 4) PLEASE SHOW ALL LOCATIONS OF | | | ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING FACILITIES. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS, | | | CLASS A,B OR C. | | | | | | 6) PLEASE INCLUDE ALL NEW SHEETS WHEN | | | SUBMITTING PLANS. | | | | | | 7) STAIRS AND RAMP SHALL HAVE HANDRAILS | | | ON BOTH SIDES. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|