Plan Review Notes
Plan Review Notes For Permit 05080168
Permit Number 05080168
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-12 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE CORRELATE "FOOT PRINT" OF BLDG ON
 ELECTRICAL PLANS TO MATCH NEW PROPOSED
 "FOOT PRINT" SHOWN ON BLDG PLANS.
  
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 PLEASE SEE FIRE REVIEW COMMENTS FOR EM/
 EXT LTS TO BE SHOWN.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SHOW ANY EXISTING RECEPTS W/ AN
 "E".
 PLEASE COMPLETE ALL SWITCH LEGS. MEANS
 OF CONTROL IS SHOWN FOR SOME LTS,
 HOWEVER THERE ARE MANY FIXTURES SHOWN
 WHICH DO NOT SEEM TO INDICATE HOW THEY
 ARE BEING CONTROLLED.
  
 PLEASE SEE ELECTRICAL PLANS ARE NOT
 COMPLETE FOR A FULL REVIEW.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD/VOIDED SHEETS ARE TO BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  