| Date |
Text |
| 2005-08-12 00:00:00 | ********** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS. |
| | PLEASE CORRELATE "FOOT PRINT" OF BLDG ON |
| | ELECTRICAL PLANS TO MATCH NEW PROPOSED |
| | "FOOT PRINT" SHOWN ON BLDG PLANS. |
| | |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | TO BE SUBMITTED. |
| | PLEASE SEE FIRE REVIEW COMMENTS FOR EM/ |
| | EXT LTS TO BE SHOWN. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM/ |
| | EXT LTS.THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE SHOW ANY EXISTING RECEPTS W/ AN |
| | "E". |
| | PLEASE COMPLETE ALL SWITCH LEGS. MEANS |
| | OF CONTROL IS SHOWN FOR SOME LTS, |
| | HOWEVER THERE ARE MANY FIXTURES SHOWN |
| | WHICH DO NOT SEEM TO INDICATE HOW THEY |
| | ARE BEING CONTROLLED. |
| | |
| | PLEASE SEE ELECTRICAL PLANS ARE NOT |
| | COMPLETE FOR A FULL REVIEW. |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS ARE TO BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | |