| Plan Review Notes For Permit 05080151 |
| Permit Number |
05080151 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1-INFORMATION SUBMITTED INDICATES THAT | | | ONE ACCORDION SHUTTER IS GOING TO BE | | | INSTALLED. RITEWAY WINDOWS & DOORS INC | | | LICENSE IS FOR GLASS & GLAZING. NEED | | | SEPARATE PERMIT BY ALUMINUM SPECIALTY | | | CONTRACTOR TO INSTALL SHUTTERS. SEE | | | COUNTY DESCRIPTION AND SCOPE OF WORK FOR | | | U-LICENSES. | | | | | | 2- SHUTTER CONTRACTOR TO PROVIDE THE | | | FOLLOWING INFORMATION: | | | A) INDICATE ON DRAWINGS SPECIFIC | | | MOUNTING CONDITIONS. | | | B) CLEARLY MARK ANCHOR TYPE AND SPACING | | | TO BE USED ACCORDING TO THE DESIGN | | | PRESSURES, EDGE DISTANCE, PANEL SPAN, | | | CONNECTION TYPE AND STRUCTURE TO BE | | | ATTACHED TO (MASONRY, CONCRETE OR WOOD) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|