| Plan Review Notes For Permit 05080148 |
| Permit Number |
05080148 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-27 00:00:00 | ********UNSAT ********** | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW AND NEW NOTES. | | | | | | | | | | | | 1)NOTE: PLEASE RE-FIGURE LOAD | | | CALCULATIONS AFTER SEEING FOLLOWING | | | NOTES.220, 215.5 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT ON 2 | | | FT OF WALL IN BEDRM #2 STILL MISSING. | | | 210.52 | | | | | | 3)NOTE: PLEASE SEE ALL DEDICATED | | | CIRCUITS LISTED IN "THEATRE" ARE STILL | | | NOT SHOWN ON PANEL SCHEDULES OR FIGURED | | | INTO LOAD CALCUALTIONS, PLEASE SEE | | | NUMEROUS DEDICATED CIRCUITS?? | | | 215.5 | | | | | | 4)NOTE: PLEASE SEE MEANS OF EGRESS | | | LIGHTING FOR THEATRE IS NOT CLARIFIED ON | | | PLANS??? | | | 210.70, LS 101 7.8 | | | | | | 5)NOTE: PLEASE SEE BATH GFI CIRCUIT ON | | | PANEL SCHEDULE SHOWN AS #14 AWG ON 15A | | | OCP. | | | 210.11C3, 20A #12. | | | | | | PLEASE KNOW, THE ABOVE ITEMS MAY BE | | | SET-UP AS A "PROVISO " IF PLANS PASS ALL | | | OTHER TRADES. IF PLANS COME BACK FOR ANY | | | COMMENTS , PLEASE ADDRESS AT THIS TIME. | | | | | | PLEASE CALL, IF THERE ARE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|