| Plan Review Notes For Permit 05080148 |
| Permit Number |
05080148 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-10-05 00:00:00 | DENIED | | | | | | 1) THE ARCHED FIXED GLASS WINDOW IN THE | | | MASTER BATH IS 42 SQFT (6' X 7'). THE | | | LARGEST AREA ALLOWED BY THE PRODUCT | | | APPROVAL SUBMITTED IS 32 SQFT. | | | | | | 2) THE NOTE ON A1 OF THE PLANS FOR THE | | | TRANSOM ABOVE THE GREAT ROOM FRENCH | | | DOORS SPECIFIES NOA 03-0508.01. THIS | | | WINDOW IS SMALL MISSLE IMPACT RATED ONLY | | | AND IS REQUIRED TO BE SHUTTERED IF BELOW | | | 30 FEET. REVISE PLANS IF LARGE MISSLE | | | IMPACT IS DESIRED. | | | | | | 3) SPECIFY THE LENGTH/EMBED DEPTH OF THE | | | ANCHOR BOLTS FOR THE BEAM HANGER IN | | | DETAIL R ON A6. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|