Plan Review Notes
Plan Review Notes For Permit 05080148
Permit Number 05080148
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-17 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE LOAD CALCUALTIONS,
 PLEASE SEE LOAD ON PANEL "A" IS SHOWN
 HIGHER THAN PANEL "B", HOWEVER FINAL
 AMERAGE IS LOWER?
 PLEASE GO OVER LOAD CALCS FOR BOTH WITH
 THE ADDED LOAD OF THE RECESSED LTS.
 PLEASE SEE NEXT COMMENT ALSO.
 215.5
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES/LOAD
 CALCULATIONS DO NOT INCLUDE THE A/C
 SYSTEM #3 AS SHOWN ON PLANS.?
 PLEASE INCLUDE AND ADJUST LAOD
 CALCULATIONS.
 215.5,220
  
 3)NOTE: PLEASE SEE NEW THEATER IS NOT
 SHOWING ANY MEANS OF EGRESS LIGHTING FOR
 ROOM? 210.70,LS 101 5-8
 PLEASE ALSO SEE THERE ARE NUMEROUS
 DEDICATED RECEPTS, CIRCUITS SHOWN ON
 PLANS, HOWEVER THESE ARE NOT SHOWN IN
 LOAD CALCULATIONS/PANEL SCHEDULE?
 PLEASE SEE POPCORN MAKER? ETC.
 1440W FOR 15A CIRCUITS, 1920W FOR 20A
 CIRCUITS.
 PLEASE ADJUST LOAD CALCULATIONS.
 215.5,220
  
 4)NOTE: PLEASE SEE SMOKE DETECTOR FOR
 MASTER BEDRM MUST BE MOVED INTO BEDRM
 AREA. PLEASE SEE NFPA-72 2-3 FOR
 LOCATION PLACEMENT.
 MUST BE LOCATED WITHIN 3' ON A SLOPED
 CEILING TO THE PEAK.
 PLEASE ALSO SEE IF WALL MOUNTED, ETC
 MUST BE 4-12" OF CEILING, ALSO 18" OF
 TOTAL CEILING HEIGHT.
  
 5)NOTE: PLEASE SEE MISSING RECEPT(S) PER
 210.52 BEDRM #2
  
 6)NOTE: PLEASE SEE CIRCUIT FOR WHIRLPOOL
 GFI IS SHOWN ON PANEL/LOAD CALCS,
 HOWEVER THIS GFI/RECEPT COULD NOT BE
 LOCATED ON PLANS.
 PLEASE SHOW.
  
 7)NOTE: PLEASE VERIFY LOADS/MOTOR LOADS
 FOR GARAGE DOOR OPENERS, PLEASE SEE ALL
 THREE MOTORS ARE SHOWN ON ONE CIRCUIT
 WITH ONLY A 400W LOAD.
 PLEASE SEE 430.53 FOR MULTIPLE MOTORS ON
 ONE CIRCUIT.
 PLEASE VERIFY HP RATING ETC OF MOTORS TO
 BE USED.
  
 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS SURVEY IS REQUIRED TO HAVE THE
 ORIGINAL SIGNATURE AND RAISED SEAL OF
 SURVEYOR. FS 472.025, FAC 61G17-17.002
 COPY.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE BE SURE TO SUBMIT ONE SET OF ALL
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-08-16 00:00:00PLANS BE BE UNSAT.
 NOTES TO FOLLOW.