| Date |
Text |
| 2005-08-17 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE LOAD CALCUALTIONS, |
| | PLEASE SEE LOAD ON PANEL "A" IS SHOWN |
| | HIGHER THAN PANEL "B", HOWEVER FINAL |
| | AMERAGE IS LOWER? |
| | PLEASE GO OVER LOAD CALCS FOR BOTH WITH |
| | THE ADDED LOAD OF THE RECESSED LTS. |
| | PLEASE SEE NEXT COMMENT ALSO. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULES/LOAD |
| | CALCULATIONS DO NOT INCLUDE THE A/C |
| | SYSTEM #3 AS SHOWN ON PLANS.? |
| | PLEASE INCLUDE AND ADJUST LAOD |
| | CALCULATIONS. |
| | 215.5,220 |
| | |
| | 3)NOTE: PLEASE SEE NEW THEATER IS NOT |
| | SHOWING ANY MEANS OF EGRESS LIGHTING FOR |
| | ROOM? 210.70,LS 101 5-8 |
| | PLEASE ALSO SEE THERE ARE NUMEROUS |
| | DEDICATED RECEPTS, CIRCUITS SHOWN ON |
| | PLANS, HOWEVER THESE ARE NOT SHOWN IN |
| | LOAD CALCULATIONS/PANEL SCHEDULE? |
| | PLEASE SEE POPCORN MAKER? ETC. |
| | 1440W FOR 15A CIRCUITS, 1920W FOR 20A |
| | CIRCUITS. |
| | PLEASE ADJUST LOAD CALCULATIONS. |
| | 215.5,220 |
| | |
| | 4)NOTE: PLEASE SEE SMOKE DETECTOR FOR |
| | MASTER BEDRM MUST BE MOVED INTO BEDRM |
| | AREA. PLEASE SEE NFPA-72 2-3 FOR |
| | LOCATION PLACEMENT. |
| | MUST BE LOCATED WITHIN 3' ON A SLOPED |
| | CEILING TO THE PEAK. |
| | PLEASE ALSO SEE IF WALL MOUNTED, ETC |
| | MUST BE 4-12" OF CEILING, ALSO 18" OF |
| | TOTAL CEILING HEIGHT. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPT(S) PER |
| | 210.52 BEDRM #2 |
| | |
| | 6)NOTE: PLEASE SEE CIRCUIT FOR WHIRLPOOL |
| | GFI IS SHOWN ON PANEL/LOAD CALCS, |
| | HOWEVER THIS GFI/RECEPT COULD NOT BE |
| | LOCATED ON PLANS. |
| | PLEASE SHOW. |
| | |
| | 7)NOTE: PLEASE VERIFY LOADS/MOTOR LOADS |
| | FOR GARAGE DOOR OPENERS, PLEASE SEE ALL |
| | THREE MOTORS ARE SHOWN ON ONE CIRCUIT |
| | WITH ONLY A 400W LOAD. |
| | PLEASE SEE 430.53 FOR MULTIPLE MOTORS ON |
| | ONE CIRCUIT. |
| | PLEASE VERIFY HP RATING ETC OF MOTORS TO |
| | BE USED. |
| | |
| | 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS SURVEY IS REQUIRED TO HAVE THE |
| | ORIGINAL SIGNATURE AND RAISED SEAL OF |
| | SURVEYOR. FS 472.025, FAC 61G17-17.002 |
| | COPY. |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE BE SURE TO SUBMIT ONE SET OF ALL |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-08-16 00:00:00 | PLANS BE BE UNSAT. |
| | NOTES TO FOLLOW. |