| Plan Review Notes For Permit 05080115 |
| Permit Number |
05080115 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-16 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON RESPONSIBLE FOR THE | | | ELECTRICAL DESIGN MUST PRINT AND SIGN | | | THEIR NAME TO THE PLAN THEY | | | DESIGNED.104.2.1 FBC. | | | | | | 2} PLEASE INDICATE LOCATION OF | | | DISCONNECT PER 225.31. | | | | | | 3} INDICATE GEC SYSTEM PER 250.32. | | | | | | 4} THE RECEPTACLES IN A ACCESSORY | | | STRUCTURE MUST BE GFCI PROTECTED PER | | | 210.8(A)(2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | |
|