Plan Review Notes
Plan Review Notes For Permit 05080115
Permit Number 05080115
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-16 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON RESPONSIBLE FOR THE
 ELECTRICAL DESIGN MUST PRINT AND SIGN
 THEIR NAME TO THE PLAN THEY
 DESIGNED.104.2.1 FBC.
  
 2} PLEASE INDICATE LOCATION OF
 DISCONNECT PER 225.31.
  
 3} INDICATE GEC SYSTEM PER 250.32.
  
 4} THE RECEPTACLES IN A ACCESSORY
 STRUCTURE MUST BE GFCI PROTECTED PER
 210.8(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  