| Date |
Text |
| 2005-12-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | |
| | ***FROM PREVIOUS REVIEW*** |
| | |
| | 1. ALL FIRST FLOOR UNITS SHALL COMPLY |
| | WITH REQUIREMENTS 1 THRU 7 OF THE FAIR |
| | HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT |
| | A DETAIL SHOWING COMPLIANCE WITH ALL |
| | REQUIREMENTS. INDICATE SPECIFICATION "A" |
| | OR "B" AS REQUIRED ON PAGE 7.34. THE |
| | CLEAR FLOOR SPACE FOR ALL USABLE |
| | FIXTURES SHALL BE APPLIED OR |
| | SUPERIMPOSED OVER THE FLOOR PLAN. FOR |
| | THE W/C SEE PAGE 7.43. - CLEAR FLOOR |
| | SPACE FOR THE W/C'S NOT SHOWN. |
| | 4. SHTS P2 OF 2 ALL UNITS WATER HEATER |
| | DETAIL. P/T DISCHARGE LINE SHALL NOT |
| | HAVE ANY TRAPED SECTIONS. SECTION |
| | 504.7.1. (SEE WATER HEATER NOTES). |
| | ****************NEW COMMENT************* |
| | 1B. WATER HEATER PANS ON THE FIRST FLOOR |
| | ARE NOT REQUIRED. IF INSTALLED, THE |
| | ELEVATION ABOVE GRADE FOR THE PAN SHALL |
| | BE INDICATED SO AS TO INSURE THE PAN |
| | WILL DRAIN AS THE TERMINATION OF THE PAN |
| | DRAIN IS SHOWN AS 6" ABOVE GRADE. |
| | SECTIONS 104.2.1 & 504.8. |
| | 2B. FIRST SHT P-1 IN ONE SET OUT OF |
| | SEQUENCE. INSERTED IN SET PRIOR TO |
| | ELECTRICAL SHEETS. ALL OTHER P-SHEETS |
| | ARE AFTER ELECTRICAL SHEETS. |
| | |