| 2005-09-12 00:00:00 | DENIED:BUILDING #2 |
| | UNIT #101 |
| | 1.PLEASE CLARIFY ELEVATION & DISTANCE |
| | OF THE TERMINATION OF THE EXHAUST FROM |
| | THE GARAGE IN RELATION TO THE WINDOW |
| | FROM BEDROOM #2.PER 2001 |
| | FBC(M)401.5.1, NOXIOUS EXHAUST SHALL BE |
| | TERMINATED A MINIMUN OF 10 FT FROM FRESH |
| | AIR INTAKES (I.E., DOORS OR WINDOWS). |
| | EXHAUST SHALL TERMINATE IN SUCH A MANNER |
| | AS NOT TO BE RECIRCULATED, 2001 FBC(M) |
| | 501.3. |
| | |
| | 2.RETURN AIR JUMPERS FROM THE MASTER |
| | BEDROOM ARE NOT SIZED PROPERLY.THE |
| | MASTER BEDROOM SHALL BE A MINIMUM OF 15" |
| | ROUND, 10" X 19" RECTANGLE OR EQUAL TO. |
| | RETURN AIR FROM A MASTER SUITE SHALL |
| | COMPLY WITH 2001 FBC(M)601.4 EXCEPTION |
| | #1 AND 3. |
| | |
| | 3.PLAN SHEET M-1 INDICATES 4" O.A. |
| | DUCT CONNECTING TO THE RETURN AIR PLENUM |
| | BOX BELOW THE AHU.THE DETAIL ON PLAN |
| | SHEET M-2, THE AHU MOUNTING DETAIL DOES |
| | NOT REFLECT THE RETURN AIR PLENUM BOX. |
| | THE DETAIL INDICATES AN AUXILIARY DRAIN |
| | PAN IN THE RETURN AIR PLENUM?PLEASE |
| | CLARIFY.SHOULD THE AHU CLOSET BE THE |
| | RETURN AIR PLENUM, ALL COMPONENTS OF THE |
| | CLOSET SHALL COMPLY WITH 2001 FBC(M) |
| | 602.2.1 & 2001 FBC CHAPTER 13 SUB |
| | CHAPTER 610.1.ABC.3.7. |
| | |
| | UNIT #102 |
| | 1.SEE COMMENT #1 FOR UNIT #101 |
| | 2.RETURN AIR JUMPER FROM THE MASTER |
| | SUITE SHALL BE A MINIMUM OF 14" ROUND, |
| | 10" X 16" RECTANGLE OR EQUAL. |
| | 3.SEE COMMENT #3 FOR UNIT #101. |
| | |
| | UNIT #103 |
| | SEE COMMENTS 1 THROUGH 3 FOR UNIT #101. |
| | 4.PLEASE CLARIFY THE ENERGY |
| | CALCULATIONS.BOTH UNIT # 101 & 103 ARE |
| | LOCATED ON THE GROUND LEVEL & END UNITS |
| | WITH THE SAME SQUARE FOOTAGE.UNIT #101 |
| | INDICATES A 4 TON UNTI WERE UNIT 103 IS |
| | ONLY A 3.5 TON UNIT. |
| | |
| | UNIT #201 |
| | PLEASE NOTE PLAN SHEET 6-A2 REFERENCES |
| | PLANS "4-A7GL, 4-A7GR-C & 4-A7GR", THIS |
| | SHOULD READ 6-A7GL,6A-GL-C (SHOULD BE |
| | 'GR' NOT GL) & 6-A7GR".PLEASE |
| | CORRELATE PLANS. |
| | 1.RETURN AIR FROM THE MASTER SUITE IS |
| | NOT SIZED IN ACCORDANCE WITH 2001 FBC(M) |
| | 601.4 EXCEPTION #1 & 3.RETURN AIR |
| | JUMPER SHALL BE A MINIMUM OF 16" ROUND |
| | 14" X 15" RECTANGLER OR EQUAL. |
| | |
| | 2.RETURN AIR JUMPER NOT REQUIRED FROM |
| | THE LAUNDRY AREA. |
| | |
| | 3.SEE COMMENT #3 FOR UNIT #101 |
| | |
| | 4.FAN SHUTDOWN WITH NOTIFICATION |
| | REQUIRED IN ACCORDANCE WITH 2001 |
| | FBC(M)606.2.1 & 606.4.1. |
| | |
| | UNIT #202 |
| | SEE ALL COMMENTS WITH THE EXCEPTION OF |
| | #4 FOR UNIT #201. |
| | |
| | UNIT #203 |
| | 1.RETURN AIR FROM THE MASTER SUITE |
| | SHALL BE A MINIMUM OF 18" ROUND OR EQUAL |
| | IN ACCORDANCE WITH 2001 FBC(M)601.4 |
| | EXCEPTION #1 & 3. |
| | |
| | 2.RETURN AIR NOT REQUIRED FROM THE |
| | LAUNDRY AREA. |
| | |
| | 3.SEE COMMENT #3 FOR UNIT #101. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |
| | |