| Date |
Text |
| 2006-02-16 00:00:00 | DENIED |
| | (3RD REVIEW) |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| | FLOOD ZONE. AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. |
| | |
| | 3) ADDITIONAL PERMIT FEES ARE DUE. THE |
| | CALCULATED VALUE OF THE STRUCTURE IS |
| | $674,294.00. A WESTWARD EXPANSION FEE OF |
| | $750.00 PER UNIT IS ALSO REQUIRED. |
| | |
| | 4)CONDOMINIUM V APARTMENTS.IF THE |
| | DWELLING UNITS ARE TO BE SOLD AS |
| | CONDOMINIUMS, A 'DECLARATION OF |
| | CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| | STATE FOR APPROVAL, AND THEN RECORDED |
| | WITH THE CLERK OF THE COUNTY COURT.A |
| | RECORDED COPY SHALL BE SUBMITTED TO THE |
| | CITY FOR RECORDS, ADDRESSING PURPOSES, |
| | AND TO PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S OFFICE PRIOR TO C.O. |
| | |
| | 5)UNDER STRUCTURAL DESIGN CRITERIA ON |
| | S5, THE CORRECT EDITIONS OF THE |
| | REFERENCE STANDARDS ARE ACI 318-02 AND |
| | ACI 530.1-02. PLEASE CORRECT. |
| | |
| | 6) SUBMIT SHOP DRAWINGS FOR THE |
| | EXTERIOR GUARDRAILS. SPECIFY THE |
| | ATTACHMENTS TO THE STRUCTURE. |
| | |
| | 7) PROVIDE SHOP DRAWINGS WITH |
| | STRUCTURAL DETAILS FOR THE INTERIOR |
| | GUARDRAIL AT THE SECOND FLOOR STAIRWELL |
| | OPENING. |
| | |
| | 8) THE CONSTRUCTION TYPE IS SPECIFIED AS |
| | TYPE V UNPROTECTED, UNSPRINKLERED. FBC |
| | 2001 TABLE 600 REQUIRES EXTERIOR BEARING |
| | WALLS TO BE FIRE RATED BASED ON DISTANCE |
| | TO PROPERTY LINES OR ASSUMED PROPERTY |
| | LINES. SPECIFY THE REQUIRED FIRE RATINGS |
| | AND LOCATIONS OF THE RATED WALLS. |
| | PROVIDE DETAILS AND SECTIONS OF WALLS |
| | AND SPECIFY THE LISTED ASSEMBLIES FOR |
| | THE FIRE RATED WALLS. |
| | |
| | 9) VERIFY THAT THE PERCENTAGE OF WALL |
| | AREA ALLOWED AS OPENINGS BY TABLE 600 |
| | BASED ON DISTANCE TO THE PROPERTY LINE |
| | OR ASSUMED PROPERTY LINE IS NOT |
| | EXCEEDED. |
| | |
| | 10) FBC 705 REQUIRES 3/4 HOUR OPENING |
| | PROTECTIVES FOR FIRE RATED EXTERIOR |
| | WALLS WITHIN 15' OF THE PROPERTY LINE. |
| | SPECIFY HOW COMPLIANCE WILL BE |
| | ACCOMPLISHED. |
| | |
| | 11) PLEASE REVISE NOTE 8 ON SHEET A9 |
| | SECTION 1626 IS ONLY APPLICABLE TO THE |
| | HVHZ. THE APPROPRIATE SECTION FOR AREAS |
| | OUTSIDE THE HVHZ, WHICH ARE IN THE |
| | WINDBOURNE DEBRIS REGION IS 1606.1.4. |
| | THIS SECTION REQUIRES GLAZING TO BE |
| | PROTECTED FROM WIND BOURNE DEBRIS. |
| | |
| | 12) SUBMIT PRODUCT APPROVALS FOR |
| | STRUCTURAL WINDOW MULLIONS AND ROOF |
| | COVERING MATERIAL. SPECIFY WHICH METHOD |
| | OF ATTACHMENT WILL BE USED TO FASTEN THE |
| | ROOF TILES. |
| | |
| | 13) ON SHEET A8GL THE 16' X 7' GARAGE |
| | DOOR HAS THE WRONG ID TAG. |
| | |
| | 14) THE ROOF SHEATHING FASTENING NOTES |
| | ON S4 AND S5 ARE INCORRECT. CITY |
| | AMENDMENTS TO 2001 FBC TABLE 2306.1 |
| | REQUIRE FASTENER SPACING TO BE 4"OC AT |
| | THE EDGES AND 6"OC INTERMEDIATE IN ROOF |
| | ZONE 3. PLEASE CORRECT. |
| | |
| | 15) SPECIFY THE TRUSS CONNECTORS THAT |
| | WILL BE USED TO ATTACH THE TRUSSES |
| | ABOVE THE GARAGES TO THE ONE HOUR FIRE |
| | RATED TENANT SEPARATION WALLS. PROVIDE |
| | DETAILS AND SECTION. SEE SHEET S-2. |
| | |
| | 16) SPECIFY THE TRUSS ANCHORS FOR THE |
| | THREE PLY (A12) GIRDERS AT THE EXTERIOR |
| | WALLS. TRUSS DRAWINGS SPECIFY 1795# |
| | UPLIFT. SEE SHEET S-3. |
| | |
| | 17) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALC. FORMS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |