| Plan Review Notes For Permit 05080087 |
| Permit Number |
05080087 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-01-22 08:13:28 | DENIED: UNITS 101 & 102 ONLY | | | | | | REVISION TO UNITS 101, 102, 201, & 202 - PLANS INDICATE | | | REVISING THE DUCT BOARD & FLEX DUCT TO R-4 FROM R-6 IN | | | UNITS 101 & 102.PLANS CAN NOT BE APPROVED WITHOUT | | | REVISING THE ENERGY CALCULATIONS.LETTER INDICATES | | | REVISED ENERGY CALCUALTIONS THAT ARE NOT WITH THE | | | SUBMITTAL PACKAGE. | | | | | | PLANS FOR UNITS 201 & 202 ARE APPROVED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|