| Date |
Text |
| 2005-09-13 00:00:00 | DENIED:BUILDING 1 (4 UNIT) |
| | UNIT#101 |
| | 1.PLEASE CLARIFY ELEVATION & DISTANCE |
| | OF THE TERMINATION OF THE EXHAUST FROM |
| | THE GARAGE IN RELATION TO THE WINDOW |
| | FROM BEDROOM #2.PER 2001 FBC(M) |
| | 401.5.1, NOXIOUS EXHAUST SHALL BE |
| | TERMINATED A MINIMUM OF 10 FT FROM FRESH |
| | AIR INTAKES (I.E. DOORS OR WINDOWS). |
| | EXHAUST SHALL TERMINTE IN SUCH A MANNER |
| | AS NOT TO BE RECIRCULATED, 2001 FBC(M) |
| | 501.3. |
| | |
| | 2.RETURN AIR JUMPER FROM THE MASTER |
| | BEDROOM ARE NOT SIZED PROPERLY. THE |
| | MASTER BEDROOM SHALL BE A MINIMUM OF 15" |
| | ROUND, 10" X 19", OR EQUAL TO. |
| | |
| | 3.PLAN SHEET M-1 INDICATES 4" O.A. |
| | DUCT CONNECTING TO THE RETURN AIR PLENUM |
| | BOX BELOW THE AHU.THE DETAIL ON PLAN |
| | SHEET M-2, AHU MOUNTING DETAIL DOES NOT |
| | REFLECT THE RETURN AIR PLENUM BOX.THE |
| | DETAIL INDICATES AN AUXILIARY DRAIN PAN |
| | IN THE RETURN AIR PLENUM?PLEASE |
| | CLARIFY.SHOULD THE AHU CLOSET BE THE |
| | RETURN AIR PLENUM, ALL COMPONENTS OF THE |
| | CLOSET SHALL COMPLY WITH 2001 FBC(M) |
| | 602.2.1 & 2001 FBC CHAPTER 13 SUB |
| | CHAPTER 610.1.ABC.3.7. |
| | |
| | UNIT #102 |
| | 1.SEE COMMENT #1 FOR UNIT 101 |
| | 2.RETURN AIR FROM THE MASTER SUITE IS |
| | BOARDER LINE, SHOULD BE INCREASED TO 10" |
| | X 17" RECTANGLE OR EQUAL. |
| | 3.SEE COMMENT #3 FOR UNIT 101. |
| | |
| | UNIT #201 |
| | 1.RETURN AIR NOT REQUIRED FROM THE |
| | LAUNDRY ROOM AREA. |
| | 2.SEE COMMENT #3 FOR UNIT 101. |
| | 3.FAN SHUTDOWN REQUIRED IN ACCORDANCE |
| | WITH 2001 FBC(M)606.2.1 & 606.4.1. |
| | |
| | UNIT 202 |
| | 1. RETURN AIR NOT REQUIRED FROM THE |
| | LAUNDRY ROOM AREA. |
| | 2.SEE COMMENT #3 FOR UNIT 101. |
| | 3.FAN SHUTDOWN REQUIRED IN ACCORDANCE |
| | WITH 2001 FBC(M)606.2.1 & 606.4.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |