| Date |
Text |
| 2005-08-26 00:00:00 | ***********UNSAT ************ |
| | |
| | BLDG #1. |
| | |
| | |
| | 1)NOTE: PLEASE CHECK AND VERIFY ALL SETS |
| | AND CORRECT SHEETS. PLEASE SEE ONE SET |
| | DOES NOT CONTAIN THE CORRECT 2NR FLR |
| | PLAN. (BLDG #2). |
| | |
| | 2)NOTE: PLEASE SEE APPLICATION SHOWS |
| | THESE BEING SUBMITTED AS "TOWNHOUSES"?? |
| | PLEASE SEE BUILDING REVIEW COMMENTS. |
| | THESE DO NOT SEEM TO BE CONSIDERED TRUE |
| | "TOWNHOUSES" AS DEFINED UNDER THE FBC. |
| | PLEASE SEE PALM BEACH COUNTY IMPACT FEE |
| | STAMPED INDICATES BUILDINGS AS 4 AND 6 |
| | UNIT MULTI FAMILY DWELLINGS. |
| | |
| | PLEASE SEE THE FOLLOWING COMMENT FOR |
| | ELECTRICAL SERVICE. |
| | |
| | 3)NOTE: PLEASE SEE DUE TO THESE NOT |
| | BEING CONSIDERED AS TOWNHOUSES WITH |
| | SEPARATE PROPERTY LINES, FEE SIMPLE ETC. |
| | ONLY ONE ELECTRICAL SERVICE WILL BE |
| | PERMITTED. PLEASE SEE GROUPING OF MAINS |
| | WILL BE REQUIRED FOR ALL FOUR UNITS IN |
| | THIS BLDG UNDER ONE SERVICE. |
| | PLEASE ADJUST SIZE OF SERVICE |
| | ACCORDINGLY. (SEC'S, GROUNDING, |
| | CONDUITS, ETC. |
| | 230.2,230.70,230.72,240.4,310.16 |
| | |
| | 4)NOTE: PLEASE SEE MISSING AREAS FOR |
| | EGRESS LIGHTING. PLEASE SEE SOME AREAS |
| | WHERE AS "J-BOX" IS SHOWN, A LT FIXTURE |
| | OFSOME TYPE WILL BE REQUIRED. PLEASE |
| | SEE ENTRIES, TERRACE(1ST FLR) LIV RMS, |
| | KITCHENS ETC. |
| | PLEASE SEE 2-STORY UNITS, A 3-WAY OR |
| | 4-WAY SWITCH WILL BE REQUIRED AT THE |
| | LANDINGS LOCATED IN BETWEEN FLRS. |
| | THIS IS ALSO REQUIRED FROM 210.70,LS 101 |
| | 5-8 |
| | |
| | 5)NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTORS FOR AREAS LEADING TO FLR |
| | ABOVE. PLEASE SEE ENTRY FOYER'S FOR |
| | 2-STORY UNITS. NFPA-72 8-1.4.1.6.2 |
| | PLEASE ALSO SEE SD'S FOR MASTER BEDRM |
| | SHALL BE MOED "INTO" BEDRM AREA. PLEASE |
| | SEE ALL SD'S ARE TO BE INSTALLED WITHIN |
| | 3' OF THE PEAK IN A SLOPE CEILING AND IN |
| | TRAY/ELEVATED CEILINGS WITHIN 12" OF MAX |
| | CEILING HEIGHT. |
| | NFPA-72 CHAPTER 2. |
| | PLEASE SEE SD'S ARE TO BE LOCATED NO |
| | CLOSER THAN 3' TO ANY KITCHEN OR BATH |
| | DOOR. AND 5' TO A RETURN AIR GRILL. |
| | NFAP-72 8-1.4.2 |
| | PLEASE SEE SOME OF THESE HAVE BEEN |
| | REDLINED ON ONE SET OF PLANS. |
| | |
| | 6)NOTE: PLEASE SEE SD'S ARE CIRCUITED TO |
| | KITCHEN/DINING LTS. THIS IS OK, HOWEVER |
| | PLEASE KNOW, THIS CIRCUIT WOULD BE ARC |
| | FAULT PROTECTED. PLEASE SEE THIS MEANS |
| | KITCHEN AND DINING RM LTS AS SHOWN WOULD |
| | BE INDICATED AS AFCI. |
| | PLEASE SEE SD'S MAY BE ON AN EXISITNG |
| | BEDRM ARC FAULT PROTECTED CIRCUIT. |
| | 210.12, 2002 NEC. |
| | |
| | 7)NOTE: PLEASE VERIFY OF GFI SHOWN IN |
| | KITCHEN IS "IN" THE PANTRY? PLEASE SEE |
| | KITCHENS WHEREPANTRY IS NOT SHOWN, AND |
| | A COUNTERSPACE IS ALSO NOT INDICATED?? |
| | |
| | 8)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | AND LTS FOR ELEVATOR PITAND EQUIPMENT |
| | SPACE. EACH SHALL CONTAIN DEDICATED |
| | CIRCUITS PER 620.23,620.24 |
| | |
| | 9)NOTE: PLEASE SEE PANEL "A" LOCATED IN |
| | UNIT, HOWEVER PANEL SCHEDULES INDICATES |
| | PANEL LOCATION IN GARAGE. |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS WERE |
| | REDLINED ON PLANS FOR AREAS OF NOTES. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS, WHICH MAY AFFECT |
| | ELECTRICAL PLANS. (BLDG). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-08-24 00:00:00 | IN ELECTRICAL FOR REVIEW. |