| Plan Review Notes For Permit 05080086 |
| Permit Number |
05080086 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-23 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. GENERATOR MANF. RECOMBINATIONS FOR | | | SERVICE CLEARANCE/VENILATION IN | | | FEET/INCHIS IN ALL DIRECTIONS MUST ACCM. | | | GENERATOR PERMIT APP. . | | | | | | 2.GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS, AND | | | EXHAUST MUST BE DIRECTED AWAY FROM | | | BUILDING.AND BE TEN FEET FROM PROPETY | | | LINE.2001 FBC/M 804.3.3 TERMINATION. | | | 2001 FBC/M SECTION 915 | | | REQUIREMENT OF NFPA 378.2.3.2 | | | EXHAUST SYSTEM TERMINATION. | | | | | | 3.PLAN MUST INDICATE OPENINGS IN | | | RELATION TO ELEC. GENERATOR. | | | 4..INFORMATION ON TYPE OF FUEL. | | | | | | 5. LP/NAT. GAS REQUIRE PERMIT, FROM | | | LICENS GAS CONTRACTOR. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|