| Plan Review Notes For Permit 05080086 |
| Permit Number |
05080086 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05080086 | | | ADD: 2320 TECUMSEH CIR | | | CONT:BRAILLY ELEC | | | TEL: (305)479-3971 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | GEN-RESREVIEW | | | ACTION: DENIED | | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | | PLUS PROVIDE PLANS WITH THE INFORMATION | | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | SECOND, PROVIDE INFORMATION ON THE | | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | | WILL BEUSED. | | | THE NEW SLAB AND HOLD DOWN DETAILS: | | | 104.2.1* ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | |
|